Final | 5/24/2016 | 5/24/2016 | 5/24/2016 | P | PASS |
James Ady
|
|
|
Inspection requested via web by steve ragan 480v pump disconnect. Final ok
|
Permanent Service | 3/24/2016 | 3/24/2016 | 3/24/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan corrections fixed p/s u/g n ok
|
Permanent Service | 3/15/2016 | 3/15/2016 | 3/15/2016 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 110.24 available fault current calculation required before service can be energized 250.50 grounding electrode system required
|
Electrical Rough-In | 2/26/2016 | 2/26/2016 | 2/26/2016 | P | PASS |
Eric Story
|
|
|
Underground Inspection Phone #: ###-#### Inspection requested via web by steve ragan west end underground for pump sytem ok cover
|