Final | 5/9/2016 | 5/9/2016 | 5/9/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
Rough-In Permanent Service | 3/2/2016 | 3/2/2016 | 3/2/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 2/29/2016 | 2/29/2016 | 2/29/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 230.74- Service disconnecting means shall simultaneously disconnect all ungrounded conductors. Garage 230.79- Service disconnects with not over 2 circuits shall have a minimum rating of 30 amps. Garage 300.4- Where NM cable is run through bored holes and notches in wood members that do not maintain 1 1/4" from framing surface shall be protected from physical damage. Garage BCC 4-05-23- Shall not cover prior to inspection. Insulation has started installation. Wood menbers, openings into boxes.
|