Final | 5/19/2016 | 5/19/2016 | 5/19/2016 | P | PASS |
Eric Story
|
|
|
If locked garage code is 1968. Phone #: ###-#### Inspection requested via web by ERIC CENTERS EC blank island outlet and other correction fixed final ok
|
Final | 5/18/2016 | 5/19/2016 | 5/19/2016 | A | FAIL |
Eric Story
|
|
|
If locked garage code is 1968. Phone #: ###-#### Inspection requested via web by ERIC CENTERS 210.12 all 120v receptacles and devices in devices shall have AFCI protection 210.52(5) receptacles shall not be located where countertop extends more then 6"
|
Rough-In Permanent Service | 3/21/2016 | 3/21/2016 | 3/21/2016 | P | PASS |
Rock A. Hudson
|
|
|
Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 3/14/2016 | 3/15/2016 | 3/15/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS Flex and #6 grounding electrode conductor installed for solar, need solar permit or add to existing. Receptacle outlet buried behind drywall by master shower.
|