Final | 8/24/2016 | 8/25/2016 | 8/25/2016 | P | PASS |
James Ady
|
|
|
Lockbox on electrical panel. Code is 1958. Permanent panel schedule is being generated. Please call with any questions. Phone #: ###-#### Inspection requested via web by Cortney Hopper corrections make final ok
|
Final | 8/23/2016 | 8/24/2016 | 8/24/2016 | P | FAIL |
James Ady
|
|
|
Lockbox below electrical panel. Code is 1958 if no one is onsite. Permanent electrical panel directory is being generated. Call with any questions. Phone #: ###-#### Inspection requested via web by Cortney Hopper406.12. Tamper resitant receps requied. (kiychen GFCI and wiremold receps. 314.20 Boxes set back more than 1/4in shall have sparkrings. 406.6 Receps shall have cover plates. Down bath 3 gang an back splash recep
|
Electrical Rough-In | 4/26/2016 | 4/27/2016 | 4/27/2016 | P | PASS |
Eric Story
|
|
|
Please contact Cortney Hopper@ ###-#### for lock box code and location if no one is at the residence as it is vacant. Thank you Inspection requested via web by Cortney Hopper corrections fixed rough-in ok cover
|
Electrical Rough-In | 4/25/2016 | 4/26/2016 | 4/26/2016 | P | FAIL |
Eric Story
|
|
|
I am requesting a late inspection due to limited access to the property. We will not be able to access the property until after 4 p.m. please call with any questions Phone #: ###-#### Inspection requested via web by Cortney Hopper 300.4 (d) cables slong flat framing member shall be held 1 1/4" from surface of a member 334.30 Type NM cable shall be supported every 4 1/2' 210.4 (b) each multi wire branch circuit shall have means to discconect all ungrounded cunductors
|