Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 | P | PASS |
Eric Story
|
|
|
Gate open, dog in house. When digging for foundation, I broke the electrical wire that went to my detached garage...which was just a romex wire buried in the ground. Installed a sub panel on garage. Would like to bury. Thanx, JIm Phone #: ###-#### Inspection requested via web by James Friedrich underground ok cover
|
Electrical Rough-In | 4/4/2016 | 4/4/2016 | 4/4/2016 | P | FAIL |
Eric Story
|
|
|
Gate open, dog in house. When digging for foundation, I broke the electrical wire that went to my detached garage...which was just a romex wire buried in the ground. Installed a sub panel on garage. Would like to bury. Thanx, JIm Phone #: ###-#### Inspection requested via web by James Friedrich 230.72 service disconnecting means is required for seperate services 250.23 grounding electrode system required for seperate services 334.12 type NM cable shall not be used in a wet location 408.36(d) back fed devices shall be secured in place by a listed fastener
|