Final | 7/8/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan final for pedestals ok
|
Final | 4/12/2016 | 4/13/2016 | 4/13/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 210.21(B)(3)- Where 2 or more receptacle outlets installed on branch circuit. Branch circuit rating shall not exceed rating of receptacles. * Unable to test GFCI function because service not energized.
|
Permanent Service | 4/5/2016 | 4/6/2016 | 4/6/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 2 locations ok as per Daryl Degrange. 1 ped east entrance on north side of road 1 ped west entrance on south side of road p/s u/g n ok
|
Permanent Service | 4/1/2016 | 4/4/2016 | 4/4/2016 | P | FAIL |
Rock A. Hudson
|
|
|
###-#### Steve. 110.9- Equipment intended to interupt current at fault levels shall have a interupting rating sufficient for current available at line terminals. Overcurrent devices not installed. Unable to verify. West pedistal 16,447 available fault current line to line. 4,799 AFC at east pedistal.
|
Permanent Service | 4/1/2016 | 4/1/2016 | 4/1/2016 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Called left message. Reschedule due to 2 separate services 1/4 mile apart covered under this permit. Lots have been developed and should have addresses for each service. Will get official ruling Monday.
|
Electrical Rough-In | 3/24/2016 | 3/24/2016 | 3/24/2016 | P | PASS |
Rock A. Hudson
|
|
|
Trench and conduit inspection (underground) for service at west end of facility. Call Steve Allen with any questions. Phone #: ###-#### Inspection requested via web by steve ragan West entrance at Mt Hood Ave. underground on all sides and 2 ground rods on south side near transformer rough in ok cover
|