Permit Information
Permit NumberELE16-00983
StatusExpired
Name ADAMSON BETTY J
Site Address 2693 W LEMHI ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: going to upgrade the panel from 100 amps to 200 amps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Expired2/12/20192/12/20192/12/2019PPASS
DetailsDaryl DeGrange
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
Final8/16/20168/17/20168/17/2016ANR
DetailsRock A. Hudson
Michael (Betty''s son) Phone #: ###-#### Main service ok, garage wiring yet to be done. Owner to add garage to existing permit. Notified homeowner about this process.
ELE-Request for Extension8/17/20168/17/20168/17/2016PPASS
DetailsRock A. Hudson
Michael (Betty''s son) Phone #: ###-#### Existing garage burned. New panel in garage to be wired in the future. Underground ok
Final4/26/20164/26/20164/26/2016PCANC
DetailsRex Boyles
Michael Phone #: ###-####-please call to meet needed r/i p/s
Rough-In Permanent Service4/26/20164/26/20164/26/2016PPASS
DetailsRex Boyles
Michael Phone #: ###-####-please call to meet r/i ok u. ground conduit to garage and 2" to pull box on house ok to cover. Told michael to upsize all conductors for de rating in 2" conduit ,added 3rd ground rod due to cutting off of 2nd rod, bond bushing installed in meterbase. Will look for intersysytem bond at final p/s o/h rec ok
Final4/21/20164/25/20164/25/2016PNR
DetailsBob Reichert
Micheal Phone #: ###-#### really wants p/s but did not buy grounding electrode conductor, bond bushings, weather-head, riser, conductors, burned pvc badly with torch, cut off about 1 foot of ground rod, told to finish and call for p/s
Conference4/1/20164/5/20164/5/2016PDONE
DetailsRex Boyles
Michael Phone #: ###-#### discuss best location for new electrical service to meet idaho power and NEC requirments now that he verified gas meter requirments with intermounain gas co. also
Conference3/30/20163/31/20163/31/2016ADONE
DetailsRex Boyles
Mikeal Phone #: ###-#### please call 30 minutes prior for access discuss service upgrade, ground rods, riser requirments, clearances from gas meter not good at this time.Micheal lookin into it prior to making a decision on new meter location