Final | 4/8/2016 | 4/8/2016 | 4/8/2016 | P | PASS |
Rock A. Hudson
|
|
|
Jim Phone #: ###-#### Benchmark to pull permit for adding light in hall and receptacle on 24" wall in bed. Final ok
|
Final | 4/5/2016 | 4/6/2016 | 4/6/2016 | P | FAIL |
Rock A. Hudson
|
|
|
would like call ahead; Jim Phone #: ###-#### 100- Multi-wire branch circuit shall be install to have voltage between ungrounded conductors. 240.4- Max overcurrent device on 14 ga. wire shall not exceed 15 amp. 210.52- Each wall 24" or wider shall have a receptacle outlet installed. bedroom 300.15- Ceck small hall outside bed for light wire in attic. Shall be installed in a box. 408.7- Unused breaker openings shall be closed. Replace GFCI on outsid of addition. Remove underground to receptacle on fence.
|