ELE-Aging Inspection | 6/6/2019 | 6/6/2019 | 6/7/2019 | | PASS |
Tom Saunders
|
|
|
permit finaled....see notes
|
Final | 6/7/2019 | 6/7/2019 | 6/7/2019 | P | PASS |
Tom Saunders
|
|
|
closing permit...contractor was not given access to fix corrections at time permit was pulled a new permit is pulled by another contractor and has agreed to make corrections..19-01750
|
ELE-Aging Inspection | 3/5/2019 | 3/5/2019 | 3/5/2019 | | DEFR |
Tom Saunders
|
|
|
too busy
|
Final | 4/27/2016 | 4/27/2016 | 4/27/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Inspection requested via web by Matthew White 250.28- Main bonding jumper shall be installed on existing main breaker panel. 250.53(D)(2)- underground water pipe shall have supplemental rod installed. Approved P/S to occupied with corrections to be completed for final.
|
Permanent Service | 4/27/2016 | 4/27/2016 | 4/27/2016 | P | PASS |
Rock A. Hudson
|
|
|
Inspection requested via web by Matthew White p/s o/h rec ok
|