Permit Information
Permit NumberELE16-01327
StatusFinaled
Name R M E INC
Site Address 3184 W ELDER ST
Project NameSTINKER STORES OFFICE
Customer Number 
ePlanReviewNo
Description
Alteration: Retrofit existing light fixture from fluorescent to 2x4 LED troffers ***4-28-16 as per customer added the following to the scope of work: relocate light switches and outlets in walls, install 7 floor boxes /CEV
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/19/20165/19/20165/19/2016PPASS
DetailsJames Ady
Inspection requested via web by Tyler Bowen
Corrections made. Final ok
Final5/18/20165/19/20165/19/2016AFAIL
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Tyler Bowen NEC 600.6 Disconnect for LED lettering requires to be within sight or breaker lock-out. NEC 210.8(B)(1) Bathroom receptacles requires GFCI protection NEC 422.52 Electric drinking fountain requires GFCI protection, Faulty GFCI breaker?
Final5/17/20165/18/20165/18/2016PNR
DetailsRock A. Hudson
Steve. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Open boxes above grid and dead receptacles
Electrical Rough-In5/9/20165/9/20165/9/2016APASS
DetailsRex Boyles
Steve. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy correction made r/i ok t bar ceilings
Electrical Rough-In5/6/20165/6/20165/6/2016PFAIL
DetailsRex Boyles
Steve. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy 300.11(A)(1)-identify seismic to troffers with distinguishable tags or colored wire.
Electrical Rough-In5/3/20165/4/20165/4/2016APASS
DetailsRex Boyles
Steve. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i new walls and entry soffit
Electrical Rough-In4/27/20164/28/20164/28/2016PPASS
DetailsRock A. Hudson
Added floor boxes in 3 rooms need underground inspection for pour back Friday. Phone #: ###-#### Inspection requested via web by Tyler Bowen
Called to check if permit is to cover full remodel of building or just lighting retro. Steve called from RME and informed office will addwork to this permit or pull another. Underslab for conference rm, break rm, and training rm rough in ok cover