Final | 5/19/2016 | 5/19/2016 | 5/19/2016 | P | PASS |
James Ady
|
|
|
Inspection requested via web by Tyler Bowen Corrections made. Final ok
|
Final | 5/18/2016 | 5/19/2016 | 5/19/2016 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen NEC 600.6 Disconnect for LED lettering requires to be within sight or breaker lock-out. NEC 210.8(B)(1) Bathroom receptacles requires GFCI protection NEC 422.52 Electric drinking fountain requires GFCI protection, Faulty GFCI breaker?
|
Final | 5/17/2016 | 5/18/2016 | 5/18/2016 | P | NR |
Rock A. Hudson
|
|
|
Steve. Phone #: ###-#### Inspection requested via web by Sean DeLacy Open boxes above grid and dead receptacles
|
Electrical Rough-In | 5/9/2016 | 5/9/2016 | 5/9/2016 | A | PASS |
Rex Boyles
|
|
|
Steve. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy correction made r/i ok t bar ceilings
|
Electrical Rough-In | 5/6/2016 | 5/6/2016 | 5/6/2016 | P | FAIL |
Rex Boyles
|
|
|
Steve. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy 300.11(A)(1)-identify seismic to troffers with distinguishable tags or colored wire.
|
Electrical Rough-In | 5/3/2016 | 5/4/2016 | 5/4/2016 | A | PASS |
Rex Boyles
|
|
|
Steve. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i new walls and entry soffit
|
Electrical Rough-In | 4/27/2016 | 4/28/2016 | 4/28/2016 | P | PASS |
Rock A. Hudson
|
|
|
Added floor boxes in 3 rooms need underground inspection for pour back Friday. Phone #: ###-#### Inspection requested via web by Tyler Bowen Called to check if permit is to cover full remodel of building or just lighting retro. Steve called from RME and informed office will addwork to this permit or pull another. Underslab for conference rm, break rm, and training rm rough in ok cover
|