Final | 6/9/2016 | 6/9/2016 | 6/9/2016 | P | PASS |
James Ady
|
|
|
Holly Phone #: ###-#### Final ok
|
Electrical Rough-In | 5/5/2016 | 5/6/2016 | 5/6/2016 | A | PASS |
Rock A. Hudson
|
|
|
Holly Phone #: ###-####
|
Electrical Rough-In | 5/3/2016 | 5/5/2016 | 5/5/2016 | A | FAIL |
James Ady
|
|
|
Holly Phone #: ###-#### 210.52 (a) Recepticle shall be within 6' of door way and no point along floorline shall be more than 6' from a recepticle 300.4 (d) NM cable shall be secured a min of 1 1/4" from surface of framing member Discused AFCI protection of bedroom outlets
|
Conference | 5/3/2016 | 5/4/2016 | 5/4/2016 | A | DONE |
Bob Reichert
|
|
|
Holly Phone #: ###-#### talked about wiring requirements and when to call for inspection
|