Final | 6/17/2016 | 6/20/2016 | 6/20/2016 | P | PASS |
Daryl DeGrange
|
|
|
Carl Phone #: ###-#### final ok
|
Final | 6/15/2016 | 6/17/2016 | 6/17/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Darren Phone #: ###-#### Contactor informed me that person doing finish work installed the electrical and requested inspection from previous day. Pop up receptacles in desk top shall also be tamper resistant type.
|
Final | 6/14/2016 | 6/15/2016 | 6/15/2016 | P | FAIL |
Rock A. Hudson
|
|
|
James Phone #: ###-#### 314.20- Boxes mounted in walls with a combustible material shall be flush or have extension rings installed. 406.12- All receptacles installed in a residence shall be tamper resistant type. In cabinets and pop-ups. Informed contact who is general foreman
|
Electrical Rough-In | 5/13/2016 | 5/16/2016 | 5/16/2016 | P | PASS |
Rock A. Hudson
|
|
|
Darren Phone #: ###-#### Deck area being used as library/ office. Full height cabinets each side of entrance to room, receptacles installed where wall space is present. Rough in ok cover
|