Final | 7/12/2016 | 7/13/2016 | 7/13/2016 | A | PASS |
Rock A. Hudson
|
|
|
Dan Phone #: ###-#### Inspection requested via web by Dan Hobdey Final ok
|
Electrical Rough-In | 6/1/2016 | 6/2/2016 | 6/2/2016 | A | PASS |
Eric Story
|
|
|
Ok to cover in kitchen area Phone #: ###-#### Inspection requested via web by Dan Hobdey Kitchen rough-in ok cover
|
Electrical Rough-In | 5/27/2016 | 5/27/2016 | 5/27/2016 | P | FAIL |
Eric Story
|
|
|
Dan Phone #: ###-#### 334.12 Type NM cable shall be protected from physical damage(wires hanging and installed in front of sheetrock) 334.30 Type NM cable shall be secured within 12" of a box and every 4 1/2' there after 300.4(d) cables shall not be secured closer then 1 1/4 within edge of framing member 314.29 j-boxes shall be readily acessible
|