Permit Information
Permit NumberELE16-01628
StatusFinaled
Name ENERGY ENTERPRISE GROUP LLC
Site Address 800 W IDAHO ST Unit: 120
Project NameEureka!
Customer Number614
ePlanReviewNo
Description
Alteration: Electrical for Restaurant TI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/6/20169/6/20169/6/2016PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Kerri Hamilton final ok
Final8/23/20168/23/20168/23/2016PPART
DetailsRock A. Hudson
Temp Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Front covered entrance yet to complete, temp egress lighting in place. Temp final ok for training
Final8/19/20168/22/20168/22/2016PNR
DetailsRock A. Hudson
Request for Temp occupancy . Call Ryan - ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Outdoor egress not complete in front due to auning not in place yet.
210.8- All GFCI receptacles located in ceiling around bar shall be located in a readily accessible location.
Electrical Rough-In8/4/20168/5/20168/5/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Kitchen area grid rough in ok cover
Electrical Rough-In7/18/20167/19/20167/19/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Front soffits rough in ok cover
Electrical Rough-In7/6/20167/7/20167/7/2016APASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Rough-in ok cover walls and ceiling grid except ceiling grid above hostess station and booth seating area
Conference6/21/20166/21/20166/21/2016PDONE
DetailsRock A. Hudson
Discussed clearance on HVAC unit disconnecting means and control box. As per Daryl Degrange 24" needed 18" min when no other options exist.
Conference5/24/20165/25/20165/25/2016ADONE
DetailsRock A. Hudson
8 am if possible please to coordinate with other trades
Ryan Barnes
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Discussed dedicated electrical space for panel boards. Job has been designed with duct work over panel boards limiting dedicated space. As per NEC 110.26(E) area shall be clear width and depth of equipment from floor to 6' above or to structural ceiling. Contractor to explore other locations for panels.
Also asked to change egress dor of electrical room to open out and have panic hardware installed.