Final | 8/17/2016 | 8/17/2016 | 8/17/2016 | P | PASS |
James Ady
|
|
|
The Corrections Have Been Made Lock box code is 0812 thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett Corrections made final ok
|
Final | 8/15/2016 | 8/15/2016 | 8/15/2016 | P | CANC |
James Ady
|
|
|
All Corrections Taken Care Of Lock Box Code Is 0812 Thanks Dave ###-#### >> Inspection requested via web by jason shifflett Inspection cancelled from web by: jason shifflett
|
Final | 8/12/2016 | 8/12/2016 | 8/12/2016 | P | FAIL |
James Ady
|
|
|
This House Is Ready There Is A Lock Box On The Front Porch To Access The House And The Garage The Code Is 0812. Call With Any Questions Or Concerns.. Thanks Phone #: ###-#### Inspection requested via web by jason shifflett 250.53 A rod electrodes shall have suplplemental electrode Garage panel 314.30 Thickness of metal shall be 1/16in thick.Dead front on main panel Front WP inoperable
|
Electrical Rough-In | 5/26/2016 | 5/26/2016 | 5/26/2016 | P | PASS |
James Ady
|
|
|
This Is,Already Csll With Any Questions Dave Phone #: ###-#### Inspection requested via web by jason shifflett Rough in ok to cover
|