Final | 6/4/2017 | 6/5/2017 | 6/5/2017 | P | PASS |
Rock A. Hudson
|
|
|
Rock Call when you are on your way. Thanks John Phone #: ###-#### Inspection requested via web by John Rourke Final ok
|
Electrical Rough-In | 5/3/2017 | 5/4/2017 | 5/4/2017 | A | PASS |
Rock A. Hudson
|
|
|
Underground PVC in south west end of south spoke.Is ready early am i should be on site by 8. Thanks John Phone #: ###-#### Inspection requested via web by John Rourke All underground complete. Rough in ok cover
|
Electrical Rough-In | 4/20/2017 | 4/21/2017 | 4/21/2017 | A | PASS |
Rock A. Hudson
|
|
|
underground north end west side south spur. I will be skipping the 7am safety meeting so i will be on site early if this works into your sch. Thanks John Phone #: ###-#### Inspection requested via web by John Rourke Area noted rough in ok cover
|
Electrical Rough-In | 4/17/2017 | 4/18/2017 | 4/18/2017 | A | PASS |
Rock A. Hudson
|
|
|
East side of south spur early am would be great if possible. Call when you are on your way Thanks John Phone #: ###-#### Inspection requested via web by John Rourke Area noted rough in ok cover
|
Final | 4/18/2017 | 4/18/2017 | 4/18/2017 | P | PART |
Rock A. Hudson
|
|
|
East side of south spur early am would be great if possible. Call when you are on your way Thanks John Phone #: ###-#### Inspection requested via web by John Rourke Information office TCO ok
|
Electrical Rough-In | 4/5/2017 | 4/6/2017 | 4/6/2017 | A | PASS |
Rock A. Hudson
|
|
|
Underground at north end of south wing.Please call when you are walking over early am would be great if that works for you. Phone #: ###-#### Inspection requested via web by John Rourke Area noted rough in ok cover
|
Electrical Rough-In | 11/17/2016 | 11/17/2016 | 11/17/2016 | P | PASS |
Eric Story
|
|
|
Heat Tape on water line in Parking garage Phone #: ###-#### Inspection requested via web by John Rourke Heat tape in garage ok to cover
|
Conference | 11/8/2016 | 11/9/2016 | 11/9/2016 | P | DONE |
Rock A. Hudson
|
|
|
Rock they are trying to get an ok to occupy the restrooms. Not sure what we need to do to make this happen Phone #: ###-#### Inspection requested via web by John Rourke Discussed area to have temp occupancy. Only area of building not ready is information office.
|
Final | 11/9/2016 | 11/9/2016 | 11/9/2016 | P | PART |
Rock A. Hudson
|
|
|
Rock they are trying to get an ok to occupy the restrooms. Not sure what we need to do to make this happen Phone #: ###-#### Inspection requested via web by John Rourke Information office not included. Rest of building and center area of grove ok to occupy. GFCI protection in place and 1 pole light to mount after christmas tree is set.
|
Permanent Service | 10/14/2016 | 10/14/2016 | 10/14/2016 | P | PASS |
Rock A. Hudson
|
|
|
will be ready early pm Phone #: ###-#### Inspection requested via web by John Rourke Fuse main disconnect, available fault current will post Monday. p/s u/g n ok
|
Electrical Rough-In | 10/5/2016 | 10/5/2016 | 10/5/2016 | P | PASS |
James Ady
|
|
|
restroom ceilings need ok to cover hardlid Phone #: ###-#### Inspection requested via web by John Rourke Restroom ceilings only ok to cover
|
Electrical Rough-In | 9/27/2016 | 9/28/2016 | 9/28/2016 | P | PASS |
Rock A. Hudson
|
|
|
Fountain rebar bonding and lighting piping. will be ready early pm Thanks John Phone #: ###-#### Inspection requested via web by John Rourke Areas noted rough in ok cover
|
Electrical Rough-In | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | PASS |
Rock A. Hudson
|
|
|
Bonding of fountain cans. Contact John @ ###-#### about 30mins prior to inspection. Phone #: ###-#### Inspection requested via web by Kristopher Wilson Bonding as noted rough in ok cover
|
Electrical Rough-In | 9/13/2016 | 9/14/2016 | 9/14/2016 | A | PASS |
Eric Story
|
|
|
underground north center core area. Early am if possible Thanks John Phone #: ###-#### Inspection requested via web by John Rourke North center core only underground ok cover
|
Electrical Rough-In | 9/8/2016 | 9/9/2016 | 9/9/2016 | P | PASS |
Rock A. Hudson
|
|
|
Rough In inspection for Restroom building. Phone #: ###-#### Inspection requested via web by Kristopher Wilson Walls for area noted rough in ok cover
|
Electrical Rough-In | 9/8/2016 | 9/9/2016 | 9/9/2016 | A | PASS |
Rock A. Hudson
|
|
|
Underground north east section of center core for lighting and outlets.early am if possible Thanks. Phone #: ###-#### Inspection requested via web by John Rourke Area noted rough in ok cover
|
Electrical Rough-In | 9/1/2016 | 9/2/2016 | 9/2/2016 | A | PASS |
Daryl DeGrange
|
|
|
Grounding of re bar around fountain in trench drain concrete also bonding of trench drain cover. Please call 8604010 when headed over thanks.John Phone #: ###-#### Inspection requested via web by John Rourke Rough-ok cover common bonding grid around fountain. Discussed bonding perimeter surface
|
Electrical Rough-In | 8/29/2016 | 8/30/2016 | 8/30/2016 | A | PASS |
Rock A. Hudson
|
|
|
Underground West Center Court. AM inspection. Contact John @ ###-#### Phone #: ###-#### Inspection requested via web by Kristopher Wilson Area noted around vault rough in ok cover
|
Electrical Rough-In | 8/21/2016 | 8/22/2016 | 8/22/2016 | P | PASS |
Rock A. Hudson
|
|
|
Underground north area of center core Phone #: ###-#### Inspection requested via web by John Rourke Discussed bonding around fountain area. Shall bond shell, 4 stubs for equipotential plane, metal spray housings. GFCI protection of LED lights depend on transformer type. North underground 20' to south rough in ok cover
|
Electrical Rough-In | 8/18/2016 | 8/19/2016 | 8/19/2016 | A | PASS |
Rock A. Hudson
|
|
|
Underground Center Court - North John @ ###-#### Phone #: ###-#### Inspection requested via web by Kristopher Wilson North section of circle underground and pole base rough in ok cover
|
Electrical Rough-In | 8/4/2016 | 8/5/2016 | 8/5/2016 | A | PASS |
Rock A. Hudson
|
|
|
Underground East Side of North Spur. AM early please. Phone #: ###-#### Inspection requested via web by Kristopher Wilson Area as noted underground rough in ok cover
|
Electrical Rough-In | 7/27/2016 | 7/28/2016 | 7/28/2016 | A | PASS |
Rock A. Hudson
|
|
|
U.G. inspection of the Northwest Spoke. Contact John @ ###-#### ~30 mins prior to inspection. Phone #: ###-#### Inspection requested via web by Kristopher Wilson North spur west half underground rough in ok cover
|
Electrical Rough-In | 7/8/2016 | 7/11/2016 | 7/11/2016 | A | PASS |
Rock A. Hudson
|
|
|
Underground inspection. Contact John @ ###-#### 30mins prior to inspection Phone #: ###-#### Inspection requested via web by Kristopher Wilson West underground rough in ok cover
|
Electrical Rough-In | 6/29/2016 | 6/30/2016 | 6/30/2016 | A | PASS |
Eric Story
|
|
|
Underground - South East Core John @ ###-#### Phone #: ###-#### Inspection requested via web by Kristopher Wilson southeast corner underground ok cover
|
Electrical Rough-In | 6/23/2016 | 6/24/2016 | 6/24/2016 | P | PASS |
Rock A. Hudson
|
|
|
Underground inspection. Contact John @ ###-#### 30mins prior to inspection. Phone #: ###-#### Inspection requested via web by Kristopher Wilson S.W. corner underground rough in ok cover. Discussed the outdoor receptacle outlets GFCI protection. Print shows 30ma equipment protective device, GFCI protection for personel shall be installed as per 210.8(B)(4)
|