Final | 8/5/2016 | 8/5/2016 | 8/5/2016 | P | PASS |
Eric Story
|
|
|
as per James Ady final ok
|
Final | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | FAIL |
Eric Story
|
|
|
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 314.20 recessed boxes in combustable material shall have a listed extender(back west room) 406.6 faceplates missing (master bath&west back room) 406.6(d)(2) GFCI protection for non grounded outlets(west back room , can not locate the GFCI)
|
Final | 8/2/2016 | 8/2/2016 | 8/2/2016 | P | FAIL |
James Ady
|
|
|
If you have any questions, please call Jared at ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan 406.4 D (2) c Non grounded receps shall be marked GFCI Protected AND No equipment ground. 210.12 AFCI protection required in all bedrooms. Master bed. Master bath recep East wall doesnt work.
|
Electrical Rough-In | 6/2/2016 | 6/2/2016 | 6/2/2016 | P | PASS |
James Ady
|
|
|
If you have any questions, please call Jared at ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections made rough in ok to cover
|
Electrical Rough-In | 5/31/2016 | 6/1/2016 | 6/2/2016 | A | FAIL |
Rock A. Hudson
|
|
|
There should be someone there. If you have any questions, please call Jared at ###-####, thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan 314.23- Boxes shall be secured. 2 boxes in master bed and bath hanging on wire. 314.29- All boxes shall be accessible. Box to left of fireplace appears to have no access when rocked.
|