Permit Information
Permit NumberELE16-01733
StatusFinaled
Name CRAIG VICTORIA L
Site Address 3812 N NORTH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Alteration or Repair: Rewire existing 100 amp service for accessory dwelling.to bring up to code.
Includes (sleeved) conduit for feed wire from meter through stem wall (to be poured) to new interior 100 amp breaker panel.
Also includes appropriate circuits (AFCI and/or GFCI) f
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/20/20172/21/20172/21/2017APASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Victoria Craig ok final
Electrical Rough-In11/28/201611/28/201611/28/2016PPASS
DetailsMark Moncarr
Call for access, radiant floor heat - Victoria Phone #: ###-#### ok cover
Electrical Rough-In9/29/20169/30/20169/30/2016APASS
DetailsMark Moncarr
Let me know if you need more info.
Thanks,
Brad Phone #: ###-#### Inspection requested via web by Victoria Craig rough in ok cover
Conference9/21/20169/22/20169/22/2016PCANC
DetailsMark Moncarr
would like call ahead; Victoria Phone #: ###-#### talked with homeowner
Electrical Rough-In6/5/20166/6/20166/6/2016APASS
DetailsJames Ady
Underground inspection prior to foundation being poured Phone #: ###-#### Inspection requested via web by Victoria Craig Rough in underground only ok to cover
Permanent Service6/1/20166/3/20166/3/2016PFAIL
DetailsJames Ady
If possible, please text/call (Brad) with estimated time.
Consult/sign-off for sleeved conduit for 100 amp sub-feed to existing accessory dwelling prior to pouring foundation.250.53 2 Suplemental electrode required. 250.25. Electrodes shall be 6ft apart. 300.18 Raceways shall be installed in complete runs. 352 .56. All joints between boxes shall be made with approved fittings 250.62 grounding electrode conductor shall be supported and protected from damage
Thank you,
Brad Phone #: ###-#### Inspection requested via web by Victoria Craig
Permanent Service5/31/20166/2/20166/1/2016PCANC
DetailsJames Ady
Please text/call, if possible, with estimated time.
Need consult/sign-off for conduit/sleeve that will go through foundation (stem wall), to be poured.
Thank you,
Brad Phone #: ###-#### >> Inspection requested via web by Victoria Craig Inspection cancelled from web by: Victoria Craig