Final | 7/18/2017 | 7/18/2017 | 7/18/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores...
ok to final
|
Final | 7/6/2017 | 7/7/2017 | 7/7/2017 | A | NR |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores...
corrections not made
|
Final | 6/27/2017 | 6/27/2017 | 6/27/2017 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores...
1) A/C OCPD is to large..needs sized to nameplate 2) sub panel needs completely labelled 3) rated boxes for exterior need installed on m/c subs..westside of building 4) broken bell box with exposed wires needs fixed...southside of building 5) strap on riser pipe at service...requested on previous inspection 6) second rod at service needs completely installed
|
Rough-In Permanent Service | 1/31/2017 | 2/1/2017 | 2/1/2017 | P | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by cris flores OCPD required and access to look at sub-panel required
|
Rough-In Permanent Service | 1/23/2017 | 1/24/2017 | 1/23/2017 | A | PASS |
Tom Saunders
|
|
|
Inspection requested via web by cris flores...
2nd ground rod will need added and strap for main riser pipe within 3' of meter can
p/s u/g rec ok
|
Electrical Rough-In | 6/6/2016 | 6/7/2016 | 6/7/2016 | P | PASS |
Eric Story
|
|
|
Wall cover Phone #: ###-#### Inspection requested via web by cris flores Interior ok cover and u/g from meter pack to sub panel ok cover aswell
|