Final | 6/15/2016 | 6/15/2016 | 6/15/2016 | P | PASS |
Eric Story
|
|
|
Joe Phone #: ###-#### Final ok
|
Final | 6/7/2016 | 6/8/2016 | 6/8/2016 | A | CANC |
Rock A. Hudson
|
|
|
Joe Phone #: ###-#### Needed permanent service.
|
Permanent Service | 6/8/2016 | 6/8/2016 | 6/8/2016 | P | PASS |
Rock A. Hudson
|
|
|
Joe Phone #: ###-#### p/s u/g n ok
|
Final | 6/6/2016 | 6/6/2016 | 6/6/2016 | P | FAIL |
Eric Story
|
|
|
Joe Phone #: ###-#### 110.9 available fault current calculation required proir 110.16 Arc flash hazard warning required 400.5 #6 soo cord is rated at 45 amp not 50
|