Final | 9/23/2016 | 9/26/2016 | 9/26/2016 | A | PASS |
Eric Story
|
|
|
Lock box code is 4750. Call Jared with any questions ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Corrections fixed final ok
|
Final | 9/20/2016 | 9/21/2016 | 9/21/2016 | A | FAIL |
Eric Story
|
|
|
Lockbox 4750 Phone #: ###-#### Inspection requested via web by Clay Morgan 210.8 GFCI shall be readily accessible 110.25 lockout for hood
|
Permanent Service | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | PASS |
Eric Story
|
|
|
If you have any questions, please call Jared ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan correction fixed final ok proper labels will be in place for final p/s o/h rec ok
|
Permanent Service | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | FAIL |
Rock A. Hudson
|
|
|
If you have any questions, please call Jared ###-####. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan 110.14- Dissimilar metals shall not be in contact with each other. 110.22- Each disconnecting means shall be identified as to it purpose.
|
Electrical Rough-In | 7/25/2016 | 7/26/2016 | 7/26/2016 | A | PASS |
Rock A. Hudson
|
|
|
Please call Clay at ###-#### so he can meet you there. Thank You!! Phone #: ###-#### Inspection requested via web by Clay Morgan Unit insulated prior to inspection. Removed where needed. Rough in ok cover
|
Electrical Rough-In | 7/25/2016 | 7/26/2016 | 7/25/2016 | A | CANC |
Rock A. Hudson
|
|
|
If you have any questions, please call Clay at ###-####. Thank You!! Phone #: ###-#### >> Inspection requested via web by Clay Morgan Inspection cancelled from web by: Clay Morgan
|
Conference | 6/8/2016 | 6/8/2016 | 6/8/2016 | P | DONE |
Rock A. Hudson
|
|
|
Please call Clay to meet you ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Discussed electrical requirements for burned out appartments. Current code required on all circuitry needing to be replaced. Tamper resistant, AFCI for rewired bedroom areas, 2 apartments full rewires and 2 partial rewires. If untouched original wiring and codes acceptable for those areas.
|