Final | 10/3/2016 | 10/4/2016 | 10/4/2016 | A | PASS |
Mark Moncarr
|
|
|
James Phone #: ###-#### final ok
|
Conference | 7/7/2016 | 7/8/2016 | 7/8/2016 | A | DONE |
James Ady
|
|
|
James Phone #: ###-#### Spoke about disconnecting means on Detached garage, Need for grounding electrode connection on all arrays, EMT requirments, Labeling requirments, and listing of equipment.
|
Conference | 7/6/2016 | 7/6/2016 | 7/6/2016 | P | DONE |
James Ady
|
|
|
Called and left message explaining the need for over current protection and disconnect on ungrounded DC cable from Solar array as well as EMT requirments and grounding of array panels
|
Conference | 7/5/2016 | 7/5/2016 | 7/5/2016 | P | DONE |
James Ady
|
|
|
Call 30 mins before // James Phone #: ###-#### Spoke to home owner about Location of inverter, Sch 80 PVC where ran above ground, Disconect on the outside of house next to meter and posibility of needing disconnect/ overloads at solar panels.
|