Final | 9/22/2017 | 9/25/2017 | 9/25/2017 | A | PASS |
Mark Moncarr
|
|
|
Megan-wife Phone #: ###-####-please call prior for access Ok final. Hottub disconnect is present, no hottub. GFI recept for tub works properly.
|
Electrical Rough-In | 7/5/2016 | 7/5/2016 | 7/5/2016 | P | PASS |
James Ady
|
|
|
Eddy Phone #: ###-#### Corrections made. Rough in ok to cover Powder bath/ laundry room only
|
Electrical Rough-In | 7/3/2016 | 7/5/2016 | 7/5/2016 | A | FAIL |
James Ady
|
|
|
Please call first so I can get you in. Thanks Eddy ###-#### Phone #: ###-#### Inspection requested via web by Eddy Udry 680.34 Recepticle shall not be located less than 6ft from inside wall of hot tub 680.12 Diconnecting means shall be located at least 5ft from inside wall and within sight
|