Temporary Service | 7/7/2016 | 7/8/2016 | 7/8/2016 | A | PASS |
Rock A. Hudson
|
|
|
Re-inspection on the temp power pole. Contact Craig Timmons @ ###-#### Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek t/s o/h n ok
|
Temporary Service | 7/6/2016 | 7/7/2016 | 7/7/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Temp Power pole Phone #: ###-#### Inspection requested via web by Cathy Duchek 400.5- Max overcurrent device for #8 3 conductor flexible cord 35 amps 50 amp installed. 590.6(B)- All temp power other than 120 volt receptacles shall have GFCI protection. Verbal with contact,
|