Electrical Rough-In | 7/18/2016 | 7/19/2016 | 7/19/2016 | A | FAIL |
Eric Story
|
|
|
Nail plates installed and grounding conductor run from outside to inside. Phone #: ###-#### Inspection requested via web by Zac Bentz too many violations to list. need kitchen layout or hire a contractor to finish project
|
Electrical Rough-In | 7/17/2016 | 7/18/2016 | 7/18/2016 | A | FAIL |
James Ady
|
|
|
There should be a contractor there, but if not, then there is a key in the mailbox. Feel free to let yourself in. 334.15 B NM cable shall be protected from physical damage. Grounding condutor shall be ran from main service to sub panel
We have decided to put the garage conversion on hold for the moment, and might pursue at a later date. Phone #: ###-#### Inspection requested via web by Zac Bentz
|
Conference | 7/6/2016 | 7/7/2016 | 7/7/2016 | A | DONE |
James Ady
|
|
|
Please call me to set up a time. Phone #: ###-#### Inspection requested via web by Zac Bentz Spoke about Tamper resistant outlets, Apliance circuit requirements, Panel update requirements.
|