Final | 1/19/2018 | 1/22/2018 | 1/22/2018 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Stephens Ok final garage.
|
Electrical Rough-In | 7/27/2016 | 7/28/2016 | 7/28/2016 | P | PASS |
James Ady
|
|
|
Reinspect Phone #: ###-#### Inspection requested via web by Bob Stephens Rough in ok to cover
|
Final | 7/27/2016 | 7/28/2016 | 7/27/2016 | P | CANC |
James Ady
|
|
|
Reinspect Phone #: ###-#### >> Inspection requested via web by Bob Stephens Inspection cancelled from web by: Bob Stephens
|
Electrical Rough-In | 7/11/2016 | 7/12/2016 | 7/12/2016 | A | FAIL |
James Ady
|
|
|
Rough electrical on Garage 1 Phone #: ###-#### Inspection requested via web by Bob Stephens 210.52 G 1. Atleast 1 recepticle shall be installed for each car space 210.52. Required recepticles shall be in addition to outlets installed above 5 1/2ft.
|