DOC - Permit Expired | 2/14/2019 | 2/14/2019 | 2/14/2019 | P | PASS |
Daryl DeGrange
|
|
|
No activity within 180 days. This permit is EXPIRED. A new permit is required to complete this job.
|
Electrical Rough-In | 7/18/2016 | 7/19/2016 | 7/19/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson corrections made, per call and notes, ri ok for house
|
Electrical Rough-In | 7/15/2016 | 7/18/2016 | 7/18/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Jason Phone #: ###-#### 210.52- Receptacle outlets needed for wall spaces. Fixed panels of back slider are wall space and wall created by pocket door in office. 300.15- All NM cables shall terminate in a box. front patio light. 334.12- NM cable shall not be installed where subject to damage. Dining light switch leg stapled to wall surface. Contractor called end of day, stubs under house for floor receptacles, front lights to be mounted when beam layout is decided, and bed S/L fixed. Will recall.
|