Final | 11/3/2016 | 11/3/2016 | 11/3/2016 | P | PASS |
Mark Moncarr
|
|
|
Lock box is on gas meter, code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks corrections made. Final ok
|
Final | 11/1/2016 | 11/1/2016 | 11/1/2016 | P | FAIL |
Mark Moncarr
|
|
|
Lock box is on gas meter/ code is 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks 1. In-use cover needed on front porch. 2. Dining light needs fixed or replaced. Top of fixture came apart from chain.
|
Rough-In Permanent Service | 7/21/2016 | 7/21/2016 | 7/21/2016 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks Corrections made. Rough in ok. p/s u/g n ok
|
Rough-In Permanent Service | 7/20/2016 | 7/20/2016 | 7/20/2016 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks 334.30 NM Cable shall be suported witjhin 12in of box, Shall not be stapled on edge. 300.4 d NM cable shall be supported 1 1/4in from nearest edge of stud. 210.52 a 1 Recepticles shall be located 6ft from door. Back door/ Dining sliding glass
|