Final | 9/9/2016 | 9/12/2016 | 9/12/2016 | A | PASS |
Eric Story
|
|
|
Code 1618 Phone #: ###-#### Inspection requested via web by Dean Gernaat final ok
|
Electrical Rough-In | 8/29/2016 | 8/29/2016 | 8/29/2016 | P | PASS |
Eric Story
|
|
|
Need grid inspection, okay to cover grid. Lock Box 1618. Phone #: ###-#### Inspection requested via web by Dean Gernaat ceilings only ok cover
|
Rough-In Permanent Service | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | CANC |
Eric Story
|
|
|
Lock box code is 1618. Documentation requested will be onsite. Phone #: ###-#### Inspection requested via web by Dean Gernaat just needed rough-in
|
Electrical Rough-In | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | PASS |
Eric Story
|
|
|
Lock box code is 1618. Documentation requested will be onsite. Phone #: ###-#### Inspection requested via web by Dean Gernaat rough-in ok cover
|
Rough-In Permanent Service | 7/28/2016 | 7/29/2016 | 7/29/2016 | A | FAIL |
Eric Story
|
|
|
Lock Box Code 1618 Phone #: ###-#### Inspection requested via web by Dean Gernaat 300.4 bored holes that dont maintain 1 1/4" from framing members shall have a listed nail plate 590.6 all temporary receptacles shall have GFCI protection as per 517.2 informational note 3 clinics are considered patient care space 517.13 wiring shall be provided with redundent ground in all exam and treatment ares
|