Final | 8/29/2016 | 8/30/2016 | 8/30/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt final ok
|
Rough-In Permanent Service | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt rough-in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 7/25/2016 | 7/26/2016 | 7/26/2016 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt called, left message, left correction notice, NEC 334.23 shall protect nm wiring within 6' of attic access, 300.4(A)(1) shall install steel plate if edge of bored hole less than 1 1/4" from face of framing member, 110.12 A shall close unused openings in panel, 250.68 connection to grounding electrode shall be accessible
|