Electrical Rough-In | 9/22/2016 | 9/22/2016 | 9/22/2016 | P | CANC |
Eric Story
|
|
|
James// please call ahead Phone #: ###-#### needed final
|
Final | 9/22/2016 | 9/22/2016 | 9/22/2016 | P | PASS |
Eric Story
|
|
|
James// please call ahead Phone #: ###-#### final ok
|
Final | 9/2/2016 | 9/2/2016 | 9/2/2016 | P | FAIL |
James Ady
|
|
|
call ahead for access;Jim Phone #: ###-#### 440.22 C Protective device shall not be high than manufacturers rating (A/C) 210.8 A 6 All receps in kitchen shall be GFCI protected. 406.12 A All receptacles in dwelling units shall be tamper resistant
|
Electrical Rough-In | 8/25/2016 | 8/25/2016 | 8/25/2016 | P | CANC |
Rock A. Hudson
|
|
|
Call half hour before to meet there // James Phone #: ###-#### Needed permanent service inspection
|
Permanent Service | 8/25/2016 | 8/25/2016 | 8/25/2016 | P | PASS |
Rock A. Hudson
|
|
|
Call half hour before to meet there // James Phone #: ###-#### p/s o/h rec ok
|
Conference | 7/25/2016 | 7/26/2016 | 7/26/2016 | A | DONE |
Rock A. Hudson
|
|
|
would like call ahead to meet; James Phone #: ###-#### Discussed service change. Moving down off of steps with meter main and panel on interior to be located out of closet area and into bed wall. Old panel locations to be junctin points. discussed mast height 6' above roof, 2 ground rods and height of meter and disconnect.
|