Final | 10/12/2016 | 10/13/2016 | 10/13/2016 | A | PASS |
Tom Saunders
|
|
|
For access back door is unlocked. Phone #: ###-#### Inspection requested via web by Terry Scott.....corrections made....ok to final
|
Final | 9/23/2016 | 9/23/2016 | 9/23/2016 | P | FAIL |
James Ady
|
|
|
Back door is unlocked, no one is living in house. Phone #: ###-#### Inspection requested via web by Terry Scott 210.70 A 3.Lighting outlet in equipment spaces. Need light in basement for furnace. 210.63 Need equipment outlet for funace. Need to install range hood
|
Electrical Rough-In | 8/4/2016 | 8/4/2016 | 8/4/2016 | P | PASS |
James Ady
|
|
|
The house is vacant and door is unlocked. Inspection requested via web by Terry Scott Kitchen/ Dining/ Up bath Rough in ok to cover
|