Final | 11/1/2016 | 11/1/2016 | 11/1/2016 | P | PASS |
Mark Moncarr
|
|
|
Lock box is on gas meter. Code is 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks final ok
|
Rough-In Permanent Service | 8/17/2016 | 8/17/2016 | 8/17/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks Corrections made Rough in ok. p/s u/g n ok
|
Rough-In Permanent Service | 8/16/2016 | 8/16/2016 | 8/16/2016 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks 210.52 B 2 The 2 or more small appliance circuits shall have no other recepts. (back patio WP) 334.30 NM cable shall be supported every4.5ft. (8-3 to range) 320.23 A Cables within 6ft from attic shall be protected from damage. 300.4 A 1. Cables through bored hole less than 1.25in from face of stud shall have nail plate. (stair half wall coner, SW Bed front corner, up hall bath,) Inspection point installed on ufer
|