Final | 2/16/2018 | 2/16/2018 | 2/16/2018 | P | PASS |
James Ady
|
|
|
Reinspection final Phone #: ###-#### Inspection requested via web by Kenneth Chapman corrections made final ok
|
Final | 12/1/2017 | 12/1/2017 | 12/1/2017 | P | PART |
James Ady
|
|
|
Final Phone #: ###-#### Inspection requested via web by Kenneth Chapman 3rd floor east hall receps dead, trash room 4sq blank, missing light 2nd floor data room,W. elec room recep, Pannel shedule in house panel,EMT straps Parking garage and Elevator room,
|
Electrical Rough-In | 11/30/2017 | 11/30/2017 | 11/30/2017 | P | PART |
James Ady
|
|
|
Rough inspection 211-220 311-320 east stairwell Phone #: ###-#### Inspection requested via web by Kenneth Chapman 211-213, 215-220, 311-320,420, All ready for final, Hall lighting on all floors ready for final, east stairway ready for final.
|
Electrical Rough-In | 11/29/2017 | 11/29/2017 | 11/29/2017 | P | PASS |
James Ady
|
|
|
Reinspect 511-520 rough inspect 201-210 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made from previous inspection. Units,200-210,300-310,400-410,500-510. ready for final
|
Electrical Rough-In | 11/29/2017 | 11/29/2017 | 11/29/2017 | A | PART |
James Ady
|
|
|
Reinspect 301-310 401-410 501-510 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 502 Missing Balcony recep,504 Burried bed recep.402 dead bed recep, 307 missing living rm light. All others ready for final
|
Electrical Rough-In | 11/28/2017 | 11/28/2017 | 11/28/2017 | A | PART |
James Ady
|
|
|
411-420 203, 205, 210, 215, 216, 218 220 303, 305, 311, 404, 419, 503,507,510 512, 519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 519 Missing patio recep,420 Bath GFCI, Kitchen Island GFCI, Barried recep left of sliding door,303 Balcony GFCI non tamper, 220 Not ready.215 Balcony GFCI. All other rooms listed have been checked and ready for final
|
Electrical Rough-In | 11/28/2017 | 11/28/2017 | 11/28/2017 | A | CANC |
James Ady
|
|
|
411-420 203, 205, 210, 215, 216, 218 220 303, 305, 311, 404, 419, 503,507,510 512, 519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Should have been building #2
|
Electrical Rough-In | 11/20/2017 | 11/20/2017 | 11/20/2017 | A | PASS |
James Ady
|
|
|
2nd floor grid inspection 5th 4th 3rd 2nd floor trash room cieling drop down inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Area listeed only ok to cover
|
Electrical Rough-In | 11/17/2017 | 11/17/2017 | 11/17/2017 | A | PASS |
James Ady
|
|
|
3rd floor grid inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman 3rd floor corridor
|
Electrical Rough-In | 11/16/2017 | 11/16/2017 | 11/16/2017 | A | FAIL |
James Ady
|
|
|
4th and fifth floor hallway grid 510-520 301-310 Phone #: ###-#### Inspection requested via web by Kenneth Chapman List of items with Fred/ Forman
|
Electrical Rough-In | 11/8/2017 | 11/8/2017 | 11/8/2017 | A | FAIL |
James Ady
|
|
|
401-410 rough Phone #: ###-#### Inspection requested via web by Kenneth Chapman 402 Balcony, Dead bed recep, Missing recep living, 401 Burried living recep, Balcony, 403 Smoke. 405 Balcony
|
Electrical Rough-In | 11/8/2017 | 11/8/2017 | 11/8/2017 | A | FAIL |
James Ady
|
|
|
501-510 rough Phone #: ###-#### Inspection requested via web by Kenneth Chapman Spark rings in all Back spashes. 502 Balcony Recep, 504 Burried recep, 501 Closet Light, Balcony, 505 Balcony, 509 Balcony.
|
Electrical Rough-In | 11/3/2017 | 11/3/2017 | 11/3/2017 | A | PASS |
James Ady
|
|
|
Garage Main floor lobby Phone #: ###-#### Inspection requested via web by Kenneth Chapman Lobby ceiling ok to cover
|
Electrical Rough-In | 10/3/2017 | 10/3/2017 | 10/3/2017 | A | PASS |
James Ady
|
|
|
Second floor Lobby rough inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Area listed only ok to cover
|
Electrical Rough-In | 9/21/2017 | 9/21/2017 | 9/21/2017 | A | PASS |
James Ady
|
|
|
211 -220 fir down soffit cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Hard lids only ok to cover
|
Electrical Rough-In | 9/18/2017 | 9/18/2017 | 9/18/2017 | A | PASS |
James Ady
|
|
|
Lobby soffit leval 3 and 4 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Hard lid only ok to cover
|
Electrical Rough-In | 9/6/2017 | 9/6/2017 | 9/6/2017 | A | PASS |
James Ady
|
|
|
Unit 317-320 fir down sofit level 1 lobby rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed ok to cover
|
Electrical Rough-In | 9/1/2017 | 9/1/2017 | 9/1/2017 | A | PASS |
James Ady
|
|
|
Sofit and fir down inspection 311-317 and coridor Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed ok to cover
|
Electrical Rough-In | 8/24/2017 | 8/24/2017 | 8/24/2017 | A | PASS |
James Ady
|
|
|
Bldg 1 units 201-208 Units 301-308 Phone #: ###-#### Inspection requested via web by Kenneth Chapman units listed ok to cover
|
Electrical Rough-In | 8/10/2017 | 8/11/2017 | 8/11/2017 | A | PASS |
James Ady
|
|
|
Drop ceilings in units 510- 520, and corridors. Phone #: ###-#### Inspection requested via web by Harley Woodward Drop hard lids only ok to cover
|
Electrical Rough-In | 8/10/2017 | 8/10/2017 | 8/10/2017 | A | CANC |
James Ady
|
|
|
Drop celings 511 through 520. Phone #: ###-#### >> Inspection requested via web by Harley Woodward Inspection cancelled from web by: Harley Woodward
|
Electrical Rough-In | 7/26/2017 | 7/27/2017 | 7/27/2017 | A | PASS |
James Ady
|
|
|
Power / panel inspections in both electrical meter rooms. Ground level. Phone #: ###-#### Inspection requested via web by Harley Woodward p/s u/g n ok
|
Electrical Rough-In | 7/25/2017 | 7/26/2017 | 7/25/2017 | A | CANC |
James Ady
|
|
|
Power / panel inspections for both electrical rooms Phone #: ###-#### >> Inspection requested via web by Harley Woodward Inspection cancelled from web by: Harley Woodward
|
Electrical Rough-In | 7/17/2017 | 7/18/2017 | 7/18/2017 | A | PASS |
James Ady
|
|
|
Drop cielings in units 201 through 210 Phone #: ###-#### Inspection requested via web by Harley Woodward Rooms listed ok to cover
|
Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 | A | PASS |
James Ady
|
|
|
Drop cieilings in rooms 301-310, and 210- 204. Phone #: ###-#### Inspection requested via web by Harley Woodward 210-204 ok
|
Electrical Rough-In | 6/26/2017 | 6/26/2017 | 6/26/2017 | A | PASS |
James Ady
|
|
|
401-410 drop ceilings for light boxes Phone #: ###-#### Inspection requested via web by Harley Woodward rm 419 and drop ceilings ok to cover
|
Electrical Rough-In | 6/22/2017 | 6/22/2017 | 6/22/2017 | A | PASS |
James Ady
|
|
|
411 through 420 appartments rough electrical (east end of building) Phone #: ###-#### Inspection requested via web by Harley Woodward could not inspect 419. Full of insulation.. Rest ok to cover
|
Electrical Rough-In | 6/15/2017 | 6/16/2017 | 6/16/2017 | A | PASS |
James Ady
|
|
|
511 trough 520 appartments (east end floor 5) Phone #: ###-#### Inspection requested via web by Harley Woodward rough in ok to cover
|
Electrical Rough-In | 6/8/2017 | 6/8/2017 | 6/8/2017 | A | PASS |
James Ady
|
|
|
Above metal framed cielings in units 501 through 510 Phone #: ###-#### Inspection requested via web by Harley Woodward Drop Ceiling only ok to cover
|
Electrical Rough-In | 5/30/2017 | 5/31/2017 | 5/31/2017 | A | PASS |
James Ady
|
|
|
Re inspect on units 211-220 and 311 -320 for corrections for rough electrical Phone #: ###-#### Inspection requested via web by Harley Woodward rough in ok
|
Electrical Rough-In | 4/27/2017 | 4/27/2017 | 4/27/2017 | A | CANC |
James Ady
|
|
|
Stairwell rough inspection Phone #: ###-#### >> Inspection requested via web by Harley Woodward Inspection cancelled from web by: Harley Woodward
|
Electrical Rough-In | 3/27/2017 | 3/28/2017 | 3/28/2017 | A | PASS |
James Ady
|
|
|
Floor #4, units 401 through 410 Phone #: ###-#### Inspection requested via web by Harley Woodward 406,407 and 408 not ready. 401-405 and 408-410 ok to cover
|
Temporary Service | 9/27/2016 | 9/28/2016 | 9/28/2016 | A | NR |
Daryl DeGrange
|
|
|
Alex Phone #: ###-#### Temp pole scheduled on electrical permit for apartment building, temp poles requires separate individual temporary service permits
|