Final | 5/2/2018 | 5/2/2018 | 5/2/2018 | A | PASS |
James Ady
|
|
|
Final reinspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman All corrections made final ok
|
Final | 4/26/2018 | 4/27/2018 | 4/27/2018 | A | PART |
James Ady
|
|
|
Final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made in all prervious inspections. 209 - 219 not inspected at this time. Exposed romex installed for garbage shoot. EMT strap needed on heater in garbage room. Partial final only! ok
|
Electrical Rough-In | 4/26/2018 | 4/26/2018 | 4/26/2018 | P | CANC |
Rock A. Hudson
|
|
|
Final inspection 5th floor 4th floor 3rd floor 2nd floor lights and Outlets exit signs in hallways garage final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman
|
Electrical Rough-In | 4/23/2018 | 4/23/2018 | 4/23/2018 | P | PASS |
James Ady
|
|
|
Corridor 2 North Corridor 3 North rough ceiling grid inspection to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Ceiling only area listed ok to cover
|
Electrical Rough-In | 4/17/2018 | 4/17/2018 | 4/17/2018 | A | PASS |
James Ady
|
|
|
Final inspection 309-319 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Rooms listed ok
|
Electrical Rough-In | 3/30/2018 | 3/30/2018 | 3/30/2018 | P | PASS |
James Ady
|
|
|
Fourth floor acoustical ceiling North inspect for cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Area liusted ok to cover
|
Electrical Rough-In | 3/30/2018 | 3/30/2018 | 3/30/2018 | A | PART |
James Ady
|
|
|
Final on 409 to 418 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 409 Missing Balcony GFCI. All other rooms listed final ok
|
Electrical Rough-In | 3/22/2018 | 3/22/2018 | 3/22/2018 | A | PART |
James Ady
|
|
|
Final inspection 509-519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 410.16C1 Surface -mounted incadescent fictures shall have 12in of clearance from face of shelf. Rooms 519,517,509,512. room 516 Bath recep non gfci protected
|
Electrical Rough-In | 3/20/2018 | 3/21/2018 | 3/21/2018 | A | PART |
James Ady
|
|
|
Electrical rough cover acoustical ceiling 4 South 3 South and 2 South hallways also roof final Phone #: ###-#### Inspection requested via web by Kenneth Chapman Hall ceiling ok to cover. Rooftop Recep N end near door dead, Main RTU missing disc. Mini split on S end 25amp max.
|
Electrical Rough-In | 3/15/2018 | 3/15/2018 | 3/15/2018 | P | PASS |
James Ady
|
|
|
Rough inspection for soffit trash room 5th floor trash room 4th floor and Lobby main floor walls Phone #: ###-#### Inspection requested via web by Kenneth Chapman Ok to cover
|
Electrical Rough-In | 3/6/2018 | 3/6/2018 | 3/6/2018 | A | PASS |
Eric Story
|
|
|
Second floor Lobby and Main ground floor Lobby fur down ready for rough inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Main floor and 2nd floor elevator lobby hard lids only ok to cover
|
Electrical Rough-In | 3/1/2018 | 3/1/2018 | 3/1/2018 | P | PASS |
Rock A. Hudson
|
|
|
4th floor Lobby fur down rough cover 3rd floor Lobby fur down rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas noted rough in ok cover
|
Electrical Rough-In | 2/23/2018 | 2/23/2018 | 2/23/2018 | P | PASS |
Rock A. Hudson
|
|
|
Electrical soffit rough 209 to 219 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Rooms noted drop lids rough in ok cover.
|
Electrical Rough-In | 2/14/2018 | 2/14/2018 | 2/14/2018 | P | PASS |
James Ady
|
|
|
Electrical rough-in 5th floor Lobby fur down electrical final 201-208 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 5th floor lobby ok to cover 203- 208 Balcony needs trimmed. 201-208 all bath fans need installed and no appliances set. all units hot checked and ready to final.
|
Electrical Rough-In | 2/8/2018 | 2/8/2018 | 2/8/2018 | P | PASS |
James Ady
|
|
|
Rough electrical soffit 309-319 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 309-320 Soffit only ok to cover
|
Electrical Rough-In | 1/25/2018 | 1/25/2018 | 1/25/2018 | P | PART |
James Ady
|
|
|
301-308 final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Countertop recep needs added in 301, All others need patio,and Dish washer pig tail installed
|
Electrical Rough-In | 1/24/2018 | 1/24/2018 | 1/24/2018 | A | PART |
James Ady
|
|
|
501-508 final electrical 401-408 final electrical 5th floor coridor grid inspection south Phone #: ###-#### Inspection requested via web by Kenneth Chapman Patio receps/ lights and backsplash spark rings missing in all units. 5th floor lid ok to cover
|
Electrical Rough-In | 1/11/2018 | 1/12/2018 | 1/12/2018 | A | PASS |
James Ady
|
|
|
Rough cover soffit 409-419 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Drop ceiling only ok to cover
|
Electrical Rough-In | 1/11/2018 | 1/11/2018 | 1/11/2018 | P | CANC |
James Ady
|
|
|
409-419 soffit rough cover Phone #: ###-#### >> Inspection requested via web by Kenneth Chapman Inspection cancelled from web by: Kenneth Chapman
|
Electrical Rough-In | 1/3/2018 | 1/3/2018 | 1/3/2018 | P | PASS |
James Ady
|
|
|
509-519 reinspect soffit rough Phone #: ###-#### Inspection requested via web by Kenneth Chapman corrections made soffits ok to cover
|
Electrical Rough-In | 1/2/2018 | 1/2/2018 | 1/2/2018 | P | FAIL |
James Ady
|
|
|
509-519 soffit rough to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Misc wire supports and unfinished items. Re-inspect rooms
|
Permanent Service | 12/12/2017 | 12/13/2017 | 12/13/2017 | A | PASS |
James Ady
|
|
|
Permanent service Phone #: ###-#### Inspection requested via web by Kenneth Chapman p/s u/g n ok
|
Permanent Service | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | NR |
James Ady
|
|
|
Permanent service north electrical meter pack 209-219, 309-319, 409-419, 509-519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Not ready. Need 2 more main breakers installed
|
Permanent Service | 12/8/2017 | 12/8/2017 | 12/8/2017 | P | PASS |
James Ady
|
|
|
Permanent service 201-208, 301-308, 401-408, 501 -508 Phone #: ###-#### Inspection requested via web by Kenneth Chapman p/s u/g n ok
|
Electrical Rough-In | 12/7/2017 | 12/7/2017 | 12/7/2017 | P | PASS |
James Ady
|
|
|
201-208 soffit rough cover South electrical room meter ser inspection for permanent service Phone #: ###-#### Inspection requested via web by Kenneth Chapman Soffits only ok to cover. Breakers checked in main service. Not ready for Perm Serv.
|
Electrical Rough-In | 11/8/2017 | 11/8/2017 | 11/8/2017 | P | PASS |
James Ady
|
|
|
301-308 rough cover soffit Phone #: ###-#### Inspection requested via web by Kenneth Chapman Drop ceiling only ok to cover
|
Electrical Rough-In | 10/26/2017 | 10/27/2017 | 10/27/2017 | P | PASS |
James Ady
|
|
|
401-408 soffit rough to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman drop ceilings only in rooms listed ok to cover
|
Electrical Rough-In | 10/26/2017 | 10/26/2017 | 10/26/2017 | P | PASS |
James Ady
|
|
|
Rough electrical re-inspect 418 419 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made rough in ok
|
Electrical Rough-In | 10/25/2017 | 10/25/2017 | 10/25/2017 | P | PART |
James Ady
|
|
|
Rough cover 409-418 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 418, 419 Add recep on kitchen counter. All others ok to cover
|
Electrical Rough-In | 10/19/2017 | 10/19/2017 | 10/19/2017 | P | PASS |
James Ady
|
|
|
Rough cover fir down 501-508 Rough cover 518 Inspection requested via web by Kenneth Chapman Reas listed only ok to cover
|
Electrical Rough-In | 10/11/2017 | 10/12/2017 | 10/11/2017 | P | PASS |
James Ady
|
|
|
Reinspect 519 rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made room 519 ok to cover
|
Electrical Rough-In | 10/11/2017 | 10/11/2017 | 10/11/2017 | P | PASS |
James Ady
|
|
|
Sairwell rough cover south and north Phone #: ###-#### Inspection requested via web by Kenneth Chapman Stairs only ok to cover
|
Electrical Rough-In | 10/9/2017 | 10/9/2017 | 10/9/2017 | P | PART |
James Ady
|
|
|
Rough cover 219 319 509-517 ; 519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 219, 319, 509-517 ok to cover. 519 missing switch by balcony slider Do not cover
|
Electrical Rough-In | 10/5/2017 | 10/5/2017 | 10/5/2017 | P | PASS |
James Ady
|
|
|
Rough cover 311 and 314 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made rough in ok
|
Electrical Rough-In | 10/4/2017 | 10/4/2017 | 10/4/2017 | P | CANC |
James Ady
|
|
|
Rough cover 209-218 309-318 Phone #: ###-#### Inspection requested via web by Kenneth Chapman
|
Electrical Rough-In | 10/4/2017 | 10/4/2017 | 10/4/2017 | P | PART |
James Ady
|
|
|
Rough cover 209-218 309-318 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 311 Missing W/P. 314 Missing KO seals in Kitchen and Living lights. Other rooms listed OK to cover
|
Electrical Rough-In | 9/15/2017 | 9/15/2017 | 9/15/2017 | P | PASS |
James Ady
|
|
|
Cieling cover coridor 2 north 3 north 4 north Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed plus 5th floor cooridor
|
Electrical Rough-In | 9/1/2017 | 9/1/2017 | 9/1/2017 | P | PASS |
James Ady
|
|
|
Corridor 301-308 and 201-208 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed ok to cover
|
Electrical Rough-In | 8/24/2017 | 8/24/2017 | 8/24/2017 | P | PASS |
James Ady
|
|
|
Bldg 2 fifth floor lobby hard lid Bldg 2 units 411-420 drop ceiling cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman areas listed ok to cover
|
Electrical Rough-In | 8/15/2017 | 8/15/2017 | 8/15/2017 | P | PART |
James Ady
|
|
|
Re inspect corrections on 501-508 Rough inspect 401-408 Phone #: ###-#### Inspection requested via web by Harley Woodward 501 kitchen lay out, 406 move door. All other rooms ok to cover
|
Electrical Rough-In | 8/10/2017 | 8/11/2017 | 8/11/2017 | P | FAIL |
James Ady
|
|
|
Units 501-508 (southwest end of building) 5th floor.
Advance warning: I canceled our inspection for today, but no one told the insulators. They started insulating before we were done. Phone #: ###-#### Inspection requested via web by Harley Woodward Misc wall spacing in kitchen countertop and next to fixed sliding door panels. Misc. nail plates on corners and SER feeds
|
Electrical Rough-In | 8/10/2017 | 8/10/2017 | 8/10/2017 | P | CANC |
|
|
|
Rooms 501 through 508 (south west end 5th floor) Phone #: ###-#### >> Inspection requested via web by Harley Woodward Inspection cancelled from web by: Harley Woodward
|
Electrical Rough-In | 5/25/2017 | 5/26/2017 | 5/26/2017 | P | FAIL |
James Ady
|
|
|
units 211-220 & 311-320 // Morgan Phone #: ###-#### 314.16. Box fill. 300.4 A 1. Cables through bored holes. 210.52 A 1 Wall spacing within 6ft of door. 250.4A2 Grounding of electrical equipment. 250.130. Grounding conductor shall be continuous. BCC Section 4-05-15 License required. Journeyman not on site at time of inspection. Apprentice working as jouneyman. Warning given
|
Electrical Rough-In | 4/27/2017 | 4/28/2017 | 4/28/2017 | P | PASS |
James Ady
|
|
|
Re inspection on rooms 201-210 (west half of building) Phone #: ###-#### Inspection requested via web by Harley Woodward Corrections made in rooms listed. Rouh in ok
|
Electrical Rough-In | 4/27/2017 | 4/27/2017 | 4/27/2017 | P | FAIL |
James Ady
|
|
|
Units 201-210 rough electrical Inspection requested via web by Harley Woodward 210.52 A 2(1) Any wall space 2ft or wider shall have recep. All Apartments 310.15 b 3 Adjustment factors For conductors without spacing for more than 24in (bundles above panels)
|
Electrical Rough-In | 4/12/2017 | 4/12/2017 | 4/13/2017 | P | PASS |
James Ady
|
|
|
3rd floor; Morgan Phone #: ###-#### NW half 3rd floor apartments only ok to cover
|
Electrical Rough-In | 4/6/2017 | 4/6/2017 | 4/6/2017 | P | PASS |
James Ady
|
|
|
Chris-re-inspection on 4th floor 405,406, 408 Phone #: ###-#### ok to cover
|
Electrical Rough-In | 3/9/2017 | 3/9/2017 | 3/9/2017 | P | PASS |
James Ady
|
|
|
Chris Phone #: ###-#### corrections made rough in Rooms 501-510 only OK to cover
|
Electrical Rough-In | 3/7/2017 | 3/8/2017 | 3/8/2017 | P | FAIL |
James Ady
|
|
|
building #2; Phone #: ###-#### 240.24 D overcurrent protection shall not be located in closets. 210.52 B 2 Small appliance circuits shall have no other outlets. Misc Recep additions and NM cable strapping. Next Inspection request needs room numbers listed.
|