Permit NumberELE16-02746
StatusFinaled
Name CONNECT BUILDING SERVICES INC
Site Address 2950 E PARKCENTER BLVD
Project NameArboretum at Barber Station
Customer Number92063
ePlanReviewNo
Description
New: Electrical for new apartment building. Station #1-to include any underground pipe work
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/2/20185/2/20185/2/2018APASS
DetailsJames Ady
Final reinspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman All corrections made final ok
Final4/26/20184/27/20184/27/2018APART
DetailsJames Ady
Final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made in all prervious inspections. 209 - 219 not inspected at this time. Exposed romex installed for garbage shoot. EMT strap needed on heater in garbage room. Partial final only! ok
Electrical Rough-In4/26/20184/26/20184/26/2018PCANC
DetailsRock A. Hudson
Final inspection 5th floor 4th floor 3rd floor 2nd floor lights and Outlets exit signs in hallways garage final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman
Electrical Rough-In4/23/20184/23/20184/23/2018PPASS
DetailsJames Ady
Corridor 2 North Corridor 3 North rough ceiling grid inspection to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Ceiling only area listed ok to cover
Electrical Rough-In4/17/20184/17/20184/17/2018APASS
DetailsJames Ady
Final inspection 309-319 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Rooms listed ok
Electrical Rough-In3/30/20183/30/20183/30/2018PPASS
DetailsJames Ady
Fourth floor acoustical ceiling North inspect for cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Area liusted ok to cover
Electrical Rough-In3/30/20183/30/20183/30/2018APART
DetailsJames Ady
Final on 409 to 418 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 409 Missing Balcony GFCI. All other rooms listed final ok
Electrical Rough-In3/22/20183/22/20183/22/2018APART
DetailsJames Ady
Final inspection 509-519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 410.16C1 Surface -mounted incadescent fictures shall have 12in of clearance from face of shelf. Rooms 519,517,509,512. room 516 Bath recep non gfci protected
Electrical Rough-In3/20/20183/21/20183/21/2018APART
DetailsJames Ady
Electrical rough cover acoustical ceiling 4 South 3 South and 2 South hallways also roof final Phone #: ###-#### Inspection requested via web by Kenneth Chapman Hall ceiling ok to cover. Rooftop Recep N end near door dead, Main RTU missing disc. Mini split on S end 25amp max.
Electrical Rough-In3/15/20183/15/20183/15/2018PPASS
DetailsJames Ady
Rough inspection for soffit trash room 5th floor trash room 4th floor and Lobby main floor walls Phone #: ###-#### Inspection requested via web by Kenneth Chapman Ok to cover
Electrical Rough-In3/6/20183/6/20183/6/2018APASS
DetailsEric Story
Second floor Lobby and Main ground floor Lobby fur down ready for rough inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman
Main floor and 2nd floor elevator lobby hard lids only ok to cover
Electrical Rough-In3/1/20183/1/20183/1/2018PPASS
DetailsRock A. Hudson
4th floor Lobby fur down rough cover
3rd floor Lobby fur down rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman
Areas noted rough in ok cover
Electrical Rough-In2/23/20182/23/20182/23/2018PPASS
DetailsRock A. Hudson
Electrical soffit rough 209 to 219 Phone #: ###-#### Inspection requested via web by Kenneth Chapman
Rooms noted drop lids rough in ok cover.
Electrical Rough-In2/14/20182/14/20182/14/2018PPASS
DetailsJames Ady
Electrical rough-in 5th floor Lobby fur down
electrical final 201-208 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 5th floor lobby ok to cover 203- 208 Balcony needs trimmed. 201-208 all bath fans need installed and no appliances set. all units hot checked and ready to final.
Electrical Rough-In2/8/20182/8/20182/8/2018PPASS
DetailsJames Ady
Rough electrical soffit 309-319 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 309-320 Soffit only ok to cover
Electrical Rough-In1/25/20181/25/20181/25/2018PPART
DetailsJames Ady
301-308 final inspection Phone #: ###-#### Inspection requested via web by Kenneth Chapman Countertop recep needs added in 301, All others need patio,and Dish washer pig tail installed
Electrical Rough-In1/24/20181/24/20181/24/2018APART
DetailsJames Ady
501-508 final electrical
401-408 final electrical
5th floor coridor grid inspection south Phone #: ###-#### Inspection requested via web by Kenneth Chapman Patio receps/ lights and backsplash spark rings missing in all units. 5th floor lid ok to cover
Electrical Rough-In1/11/20181/12/20181/12/2018APASS
DetailsJames Ady
Rough cover soffit 409-419 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Drop ceiling only ok to cover
Electrical Rough-In1/11/20181/11/20181/11/2018PCANC
DetailsJames Ady
409-419 soffit rough cover Phone #: ###-#### >> Inspection requested via web by Kenneth Chapman Inspection cancelled from web by: Kenneth Chapman
Electrical Rough-In1/3/20181/3/20181/3/2018PPASS
DetailsJames Ady
509-519 reinspect soffit rough Phone #: ###-#### Inspection requested via web by Kenneth Chapman corrections made soffits ok to cover
Electrical Rough-In1/2/20181/2/20181/2/2018PFAIL
DetailsJames Ady
509-519 soffit rough to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Misc wire supports and unfinished items. Re-inspect rooms
Permanent Service12/12/201712/13/201712/13/2017APASS
DetailsJames Ady
Permanent service Phone #: ###-#### Inspection requested via web by Kenneth Chapman p/s u/g n ok
Permanent Service12/12/201712/12/201712/12/2017PNR
DetailsJames Ady
Permanent service north electrical meter pack 209-219, 309-319, 409-419, 509-519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Not ready. Need 2 more main breakers installed
Permanent Service12/8/201712/8/201712/8/2017PPASS
DetailsJames Ady
Permanent service 201-208, 301-308, 401-408, 501 -508 Phone #: ###-#### Inspection requested via web by Kenneth Chapman p/s u/g n ok
Electrical Rough-In12/7/201712/7/201712/7/2017PPASS
DetailsJames Ady
201-208 soffit rough cover
South electrical room meter ser inspection for permanent service Phone #: ###-#### Inspection requested via web by Kenneth Chapman Soffits only ok to cover. Breakers checked in main service. Not ready for Perm Serv.
Electrical Rough-In11/8/201711/8/201711/8/2017PPASS
DetailsJames Ady
301-308 rough cover soffit Phone #: ###-#### Inspection requested via web by Kenneth Chapman Drop ceiling only ok to cover
Electrical Rough-In10/26/201710/27/201710/27/2017PPASS
DetailsJames Ady
401-408 soffit rough to cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman drop ceilings only in rooms listed ok to cover
Electrical Rough-In10/26/201710/26/201710/26/2017PPASS
DetailsJames Ady
Rough electrical re-inspect 418 419 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made rough in ok
Electrical Rough-In10/25/201710/25/201710/25/2017PPART
DetailsJames Ady
Rough cover 409-418 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 418, 419 Add recep on kitchen counter. All others ok to cover
Electrical Rough-In10/19/201710/19/201710/19/2017PPASS
DetailsJames Ady
Rough cover fir down 501-508
Rough cover 518 Inspection requested via web by Kenneth Chapman Reas listed only ok to cover
Electrical Rough-In10/11/201710/12/201710/11/2017PPASS
DetailsJames Ady
Reinspect 519 rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made room 519 ok to cover
Electrical Rough-In10/11/201710/11/201710/11/2017PPASS
DetailsJames Ady
Sairwell rough cover south and north Phone #: ###-#### Inspection requested via web by Kenneth Chapman Stairs only ok to cover
Electrical Rough-In10/9/201710/9/201710/9/2017PPART
DetailsJames Ady
Rough cover 219 319 509-517 ; 519 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 219, 319, 509-517 ok to cover. 519 missing switch by balcony slider Do not cover
Electrical Rough-In10/5/201710/5/201710/5/2017PPASS
DetailsJames Ady
Rough cover 311 and 314 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Corrections made rough in ok
Electrical Rough-In10/4/201710/4/201710/4/2017PCANC
DetailsJames Ady
Rough cover 209-218 309-318 Phone #: ###-#### Inspection requested via web by Kenneth Chapman
Electrical Rough-In10/4/201710/4/201710/4/2017PPART
DetailsJames Ady
Rough cover 209-218 309-318 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 311 Missing W/P. 314 Missing KO seals in Kitchen and Living lights. Other rooms listed OK to cover
Electrical Rough-In9/15/20179/15/20179/15/2017PPASS
DetailsJames Ady
Cieling cover coridor 2 north 3 north 4 north Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed plus 5th floor cooridor
Electrical Rough-In9/1/20179/1/20179/1/2017PPASS
DetailsJames Ady
Corridor 301-308 and 201-208 Phone #: ###-#### Inspection requested via web by Kenneth Chapman Areas listed ok to cover
Electrical Rough-In8/24/20178/24/20178/24/2017PPASS
DetailsJames Ady
Bldg 2 fifth floor lobby hard lid
Bldg 2 units 411-420 drop ceiling cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman areas listed ok to cover
Electrical Rough-In8/15/20178/15/20178/15/2017PPART
DetailsJames Ady
Re inspect corrections on 501-508
Rough inspect 401-408 Phone #: ###-#### Inspection requested via web by Harley Woodward 501 kitchen lay out, 406 move door. All other rooms ok to cover
Electrical Rough-In8/10/20178/11/20178/11/2017PFAIL
DetailsJames Ady
Units 501-508 (southwest end of building) 5th floor.

Advance warning: I canceled our inspection for today, but no one told the insulators. They started insulating before we were done. Phone #: ###-#### Inspection requested via web by Harley Woodward Misc wall spacing in kitchen countertop and next to fixed sliding door panels. Misc. nail plates on corners and SER feeds
Electrical Rough-In8/10/20178/10/20178/10/2017PCANC
Details
Rooms 501 through 508 (south west end 5th floor) Phone #: ###-#### >> Inspection requested via web by Harley Woodward Inspection cancelled from web by: Harley Woodward
Electrical Rough-In5/25/20175/26/20175/26/2017PFAIL
DetailsJames Ady
units 211-220 & 311-320 // Morgan Phone #: ###-#### 314.16. Box fill. 300.4 A 1. Cables through bored holes. 210.52 A 1 Wall spacing within 6ft of door. 250.4A2 Grounding of electrical equipment. 250.130. Grounding conductor shall be continuous. BCC Section 4-05-15 License required. Journeyman not on site at time of inspection. Apprentice working as jouneyman. Warning given
Electrical Rough-In4/27/20174/28/20174/28/2017PPASS
DetailsJames Ady
Re inspection on rooms 201-210 (west half of building) Phone #: ###-#### Inspection requested via web by Harley Woodward Corrections made in rooms listed. Rouh in ok
Electrical Rough-In4/27/20174/27/20174/27/2017PFAIL
DetailsJames Ady
Units 201-210 rough electrical Inspection requested via web by Harley Woodward 210.52 A 2(1) Any wall space 2ft or wider shall have recep. All Apartments 310.15 b 3 Adjustment factors For conductors without spacing for more than 24in (bundles above panels)
Electrical Rough-In4/12/20174/12/20174/13/2017PPASS
DetailsJames Ady
3rd floor; Morgan Phone #: ###-#### NW half 3rd floor apartments only ok to cover
Electrical Rough-In4/6/20174/6/20174/6/2017PPASS
DetailsJames Ady
Chris-re-inspection on 4th floor 405,406, 408 Phone #: ###-#### ok to cover
Electrical Rough-In3/9/20173/9/20173/9/2017PPASS
DetailsJames Ady
Chris Phone #: ###-#### corrections made rough in Rooms 501-510 only OK to cover
Electrical Rough-In3/7/20173/8/20173/8/2017PFAIL
DetailsJames Ady
building #2; Phone #: ###-#### 240.24 D overcurrent protection shall not be located in closets. 210.52 B 2 Small appliance circuits shall have no other outlets. Misc Recep additions and NM cable strapping. Next Inspection request needs room numbers listed.