Final | 1/5/2017 | 1/9/2017 | 1/9/2017 | A | PASS |
James Ady
|
|
|
Allen tray Wicks owner. 2532320401 Phone #: ###-#### Inspection requested via web by shane miller Final OK
|
Electrical Rough-In | 8/29/2016 | 8/30/2016 | 8/30/2016 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller corrections made, ri ok
|
Electrical Rough-In | 8/28/2016 | 8/29/2016 | 8/29/2016 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Inspection requested via web by shane miller called, left correction notice, NEC 314.23 shall not use screws inside box not listed for the purpose, 300.4(A) shall install steel plate if edge of bored hole is less than 1 1/4" fron edge of framing member, 334.30 shall securely fasten nm cabe within 12" of termination, 210.52(E) shall install receptacle at front and rear of dwelling
|