Final | 1/6/2017 | 1/6/2017 | 1/6/2017 | P | PASS |
Eric Story
|
|
|
Room # 17 Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
Final | 12/28/2016 | 12/29/2016 | 12/29/2016 | P | PART |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Samatha Solberg Room4 ok. 210.8A 9 Bathtubs and shower stalls. Where recept are installed within 6ft of outside edge. Room 17 needs GFCI recepts installed to the right of the tub and to the left of the shower threshold
|
Electrical Rough-In | 9/1/2016 | 9/2/2016 | 9/2/2016 | A | PASS |
Mark Moncarr
|
|
|
Good morning - Rough in inspection please. Contact will be Heather Stuckart ###-####. Please call with any questions as she may not be on the job site. Thank you so much and have a wonderful Friday. Phone #: ###-#### Inspection requested via web by Laura Longshaw ok for cover
|