Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE16-03138
StatusFinaled
Name ALL-STAR ELECTRIC
Site Address 3278 N SHAMROCK AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Trimm out only- per Daryl DeGrange, work to also include: service upgrade
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection3/21/20193/21/20193/22/2019 PASS
DetailsTom Saunders
final scheduled...see notes
Final3/22/20193/22/20193/22/2019PPASS
DetailsTom Saunders
corrections done under permit ELE17-01230
by different contractor...finaling permit to close
Conference4/12/20174/17/20174/17/2017ADONE
DetailsDaryl DeGrange
New general contactor would like to meet to discuss job history and next step to final permits. Informed 327 all previous ele contractors refuse work due to lack of payment. Tony ###-#### called this number and Julie answered. Julie ###-#### from notes on 4-12-17 inspections. Spoke with New General Contractor, discussed New Electrical contractor requirements
Final4/11/20174/12/20174/12/2017ANR
DetailsRock A. Hudson
Tony Phone #: ###-####
Work yet to finish. See RI notes
Electrical Rough-In4/11/20174/12/20174/12/2017AFAIL
DetailsRock A. Hudson
Juile ###-#### Tony Phone #: ###-####
Homeowner requested inspections.
All-star Electric has open permit ###-####.
Electrical contractor only one to request inspections under permit purchased.
210.52- Door to be framed in at entrance to bedroom shall have a receptacle outlet located with in 6'. No point measured along floor line shall be greater than 6' fram a receptacle outlet.
300.15- All wiring shall terminate in a box with cover. Old AC location next to stairway outdoors and misc covers needed inside.
400.8- Flexible cords shall not pass thru doorway, walls, or ceiling. Relocate sump pump receptacle to inside room.
410.16- Luminaires located in closets and storage area shelves shall be totally enclosed type. New closet to be built in bed with 2 cans with open type and open lamp in storage area.
422.30- Water heater shall have a disconnecting means located with in sight. Lock out acceptable as per 110.25.