Final | 11/22/2016 | 11/23/2016 | 11/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Final ok
|
Final | 11/21/2016 | 11/22/2016 | 11/22/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8(B)- All 120 volt receptacle outlets located in prep area shall have GFCI protection as stated in note 1 and 8 on print. 400.5- Flexible cord ampacity. #10 SJOOW flexible cord installed on expresso machines as per table 400.5 column B 30 amp max, 50 amp installed. 406.5(E)- Receptacle outlets shall not be installed face up in counter top surfaces unless specifically listed for area.
|
Electrical Rough-In | 11/10/2016 | 11/10/2016 | 11/10/2016 | P | PASS |
Rock A. Hudson
|
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by kendall bender Back and hall grid rough in ok cover
|
Permanent Service | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Needed rough in inspection
|
Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Main gear provided overcurrent for TI panel. 480 Volt panel and transformers and associated panels rough in ok cover
|
Electrical Rough-In | 10/10/2016 | 10/11/2016 | 10/11/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender All walls rough in ok cover
|
Electrical Rough-In | 10/3/2016 | 10/4/2016 | 10/4/2016 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Kitchen area walls only rough in ok cover
|