Final | 12/14/2016 | 12/15/2016 | 12/15/2016 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Final ok
|
Final | 12/14/2016 | 12/14/2016 | 12/14/2016 | P | PART |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Partial final only, still need wallpacks hung and wired
|
Permanent Service | 12/7/2016 | 12/7/2016 | 12/7/2016 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams....
p/s u/g n ok
|
Permanent Service | 12/2/2016 | 12/5/2016 | 12/5/2016 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams 110.24 Available fault current calculation required prior to being energized 210.4 Multi wire branch circuits shall simultaneousl disconnect all ungrounded conductors 230.6 Burial depth not deep enough will encase in 2in concrete
|
Permanent Service | 12/2/2016 | 12/2/2016 | 12/2/2016 | A | CANC |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Buidling permit hasent been issued yet
|
Electrical Rough-In | 10/20/2016 | 10/21/2016 | 10/21/2016 | A | PASS |
Eric Story
|
|
|
Ufer ground Phone #: ###-#### Inspection requested via web by Jim Williams Concrete electrode ok cover
|