Final | 12/15/2016 | 12/15/2016 | 12/15/2016 | P | PASS |
Rock A. Hudson
|
|
|
Temp power pole final ok
|
Temporary Service | 10/20/2016 | 10/20/2016 | 10/20/2016 | P | PASS |
Rock A. Hudson
|
|
|
Corrections fixed. Contact is Toby Groves. ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves t/s o/h n ok
|
Final | 10/18/2016 | 10/19/2016 | 10/19/2016 | A | CANC |
Rock A. Hudson
|
|
|
Toby Groves is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Needed temp service inspection
|
Temporary Service | 10/19/2016 | 10/19/2016 | 10/19/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Toby Groves is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 110.26- Minimum work space shall be provided for temp service. 30" wide and 36" deep in front of service. 590.6(B)- Receptacles other than 125 volt shall have GFCI protection if used for construction.
|