Final | 5/5/2017 | 5/8/2017 | 5/8/2017 | A | PASS |
Eric Story
|
|
|
House will be unlocked... Call Matt ###-#### when finished and lock door behind you. Corrections fixed final ok
|
Final | 5/5/2017 | 5/5/2017 | 5/5/2017 | P | CANC |
Eric Story
|
|
|
Matt-can''t be home until after 2:30-if you can''t go out after that please call so he can reschedule Phone #: ###-#### Will need to call in for Monday 5-8-17
|
Final | 4/25/2017 | 4/25/2017 | 4/25/2017 | P | FAIL |
Eric Story
|
|
|
would like call ahead; Matt Phone #: ###-#### 406.4 Tamper resistant receptacles required when changing out receptacles 406.4(d)(2) Non grounded receptacles shall be GFCI protected and marked No ground/GFCI protection as was discussed in conference 314.24 Spark rings required when not flush with finished material(kitchen,bath) 110.7 Complete installation shall be free from shorts(triping breaker in panel going phase to phase)
|
Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | PASS |
James Ady
|
|
|
Call before coming out. 2088637153 Inspection requested via web by Matt Smith Rough in back 2 bedrooms and laundry room ok to cover
|
Conference | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | DONE |
James Ady
|
|
|
Call before coming out. 2088637153 Inspection requested via web by Matt Smith Talked about GFCI protection of open ground receps, Tamper resistant receps and smoke detector requirments
|
Electrical Rough-In | 10/19/2016 | 10/25/2016 | 10/25/2016 | P | CANC |
Eric Story
|
|
|
Please call before heading there so I can make sure I am there to let you in Phone #: ###-#### Inspection requested via web by Matt Smith No inspection until building permit has been issued, will need to reschedule
|