Permit Information
Permit NumberELE16-03453
StatusFinaled
Name D C ELECTRICAL SOLUTIONS
Site Address 3681 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Permanent Service Up to 200 amps ONLY
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/30/20161/3/20171/3/2017APASS
DetailsRock A. Hudson
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
Final12/29/201612/30/201612/30/2016AFAIL
DetailsRock A. Hudson
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis
110.3- Devices shall be connected as per manufacturers instructions. Reverse polarity 2nd floor at top of stair.
110.25- A disconnecting means shall be provided for dishwasher and hood as per 422.30 lockout acceptable.
210.22- Receptacle rating shall not exceed branch circuit rating. 50 amp installed in dryer.
406.5- Dining receptacle shall be secured to box.
440.6- AC over current device shall not exceed that of nameplate rating. 30 amp installed on 25 amp max unit.
posted notice and had verbal with wireman on site
Rough-In Permanent Service10/27/201610/28/201610/28/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Charles Davis
Rough in ok cover p/s u/g n ok