Final | 12/30/2016 | 1/3/2017 | 1/3/2017 | A | PASS |
Rock A. Hudson
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
|
Final | 12/29/2016 | 12/30/2016 | 12/30/2016 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis 110.3- Devices shall be connected as per manufacturers instructions. Reverse polarity 2nd floor at top of stair. 110.25- A disconnecting means shall be provided for dishwasher and hood as per 422.30 lockout acceptable. 210.22- Receptacle rating shall not exceed branch circuit rating. 50 amp installed in dryer. 406.5- Dining receptacle shall be secured to box. 440.6- AC over current device shall not exceed that of nameplate rating. 30 amp installed on 25 amp max unit. posted notice and had verbal with wireman on site
|
Rough-In Permanent Service | 10/27/2016 | 10/28/2016 | 10/28/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis Rough in ok cover p/s u/g n ok
|