Final | 5/10/2017 | 5/11/2017 | 5/11/2017 | A | PASS |
Rock A. Hudson
|
|
|
unit will be unlocked Phone #: ###-#### Inspection requested via web by Robert Schroder Final ok
|
Rough-In Permanent Service | 1/26/2017 | 1/26/2017 | 1/26/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder p/s u/g n ok
|
Conference | 1/5/2017 | 1/5/2017 | 1/5/2017 | A | DONE |
Mark Moncarr
|
|
|
Phone conference please, thanks. Phone #: ###-#### Inspection requested via web by Robert Schroder Talked with contractor on phone about working clearance for his panels. Has about 34-1/2 in. in front of panels. Gave him the ok as long as it wasnt any less than that. He cannot relocate underground as it is in concrete.
|
Electrical Rough-In | 11/21/2016 | 11/21/2016 | 11/21/2016 | A | PASS |
Eric Story
|
|
|
Reinspect inground conduit for covet. Thanks Phone #: ###-#### Inspection requested via web by Robert Schroder Correction fixed underground ok cover
|
Electrical Rough-In | 11/15/2016 | 11/15/2016 | 11/15/2016 | A | FAIL |
Eric Story
|
|
|
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Robert Schroder 352.24 Bends shall be made that will not damage internal raduis of conduit Shall not scorch outer coating of PVC
|