Permit Information
Permit NumberELE16-03597
StatusFinaled
Name JES ELECTRIC
Site Address 1221 W BOISE AVE
Project Name 
Customer Number2016-12
ePlanReviewNo
Description
Alteration: Electrical Confrence
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/7/20177/7/20177/7/2017APASS
DetailsEric Story
I Took care Of The Corrections Noted And Its ready For Final, The Fixed Appliance Outlets In The Kitchen Are GFCi Breakers The Two Counter Top Outlets For Cash Registers Are A Device As They Are Accessible Without Removal Of Equipment And No Tools Required. The Outside Lights That Are Abandoned Are Down The Only Lights Left Are existing Or New In Working Order Thanks And Have A Great Day! Dave call With Any Questions Lock Box Code On Front Door Is 4290 Phone #: ###-#### Inspection requested via web by jason shifflett
Corrections fixed fnal ok
Final6/26/20176/26/20176/26/2017PFAIL
DetailsEric Story
We Are Ready For A,Final On This Job Lockbox On Front Door Code Is 4290..Please Call With Any Questions Or Concerns Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett
210.8 All receptacles located in comm kitchens shall have GFCI protection
Remove existing wiring light out back with wires hanging
Electrical Rough-In12/12/201612/12/201612/12/2016PPASS
DetailsJames Ady
We are in need of cover... should be ready for you... please give us 20 minutes notice and we can meet you there. Thanks Phone #: ###-#### Inspection requested via web by jason shifflett Rough in ok
Conference11/7/201611/7/201611/7/2016PDONE
DetailsJames Ady
I Spoke To Daryll Degrange about the project we need to have you put eyes on this project and we have questions. Please Call Me ASAP So I Can Meet You There PleaseAnd Thank You! Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Talked about need to update sub panels due to damaged bussing. Update feeder coduits to proper size and install Equipment ground