Final | 3/16/2017 | 3/16/2017 | 3/16/2017 | P | PASS |
Eric Story
|
|
|
Joe-please for access Phone #: ###-#### Correction fixed final ok
|
Final | 3/7/2017 | 3/8/2017 | 3/8/2017 | A | FAIL |
Eric Story
|
|
|
Call half hour before // Joe Phone #: ###-#### 406.12 Tamper resistant required(washing machine) 210.8 Receptacles located within 6' of sink shall have GFCI protection(backside of kitchen sink) 210.52 (d) receptacle required within 3' of sink in bathrooms
|
Electrical Rough-In | 11/15/2016 | 11/16/2016 | 11/16/2016 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Panel was removed from fire wall, Panel wall only ok cover
|
Electrical Rough-In | 11/14/2016 | 11/14/2016 | 11/14/2016 | P | PASS |
Eric Story
|
|
|
this is ready for am if possible Phone #: ###-#### House only will need to verify panel moved out of fire wall(panel area is not approved for cover until has been inspected)
|