Information based on query as of Saturday, June 29, 2024.
Permit Information
Permit NumberELE16-03933
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 505 W BROAD ST
Project Name 
Customer Number3602
ePlanReviewNo
Description
New: Full Electrical Install in the Core and Shell. Installation includes gear, panels, switchgear, boxes, wiring, receptacles, lighting and telecommunications.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/28/20182/28/20182/28/2018PPASS
DetailsRock A. Hudson
Final on all live work Units 101, 102, 103, 104, 105
Early afternoon preferred
Contact Bob Mott
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
All complete, signed off in office. Final ok
Final2/26/20182/26/20182/26/2018PPART
DetailsRock A. Hudson
Parking garage island has been removed with no plans to relocate. will do with island located at mezz. level. Court yard heat tape OK, Window trim under outdoor receptacle gasket level 3 patios, Check heat tape EPD at garage mini split locations and service receptacles. AFCI posted.
Conference1/31/20181/31/20181/31/2018PDONE
DetailsRock A. Hudson
Level 1- 106, Level 2- 202, 203, 204, 205, 206, 210, 213, 215, 216 noted as of 1-31-18
Final1/9/20181/10/20181/10/2018APART
DetailsRock A. Hudson
housing lobby 106 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Unit noted signed off in office, partial final ok
Final1/6/20181/8/20181/8/2018APART
DetailsRock A. Hudson
Bike parking 213, Restrooms 204-205, Dog wash 216, Telecom 206, Business center 202, Parcel Room 215, Management office 210, 203 fitness room Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas noted signed off in office partial final ok
Electrical Rough-In1/2/20181/2/20181/4/2018PPASS
DetailsDaryl DeGrange
Ceiling inspection cover managers office Phone #: ###-#### Inspection requested via web by Cathy Duchek rough-in ok cover ceiling grid
Electrical Rough-In12/11/201712/12/201712/12/2017APASS
DetailsRock A. Hudson
Live work #101 kitchen wall and dropped ceilings Phone #: ###-#### Inspection requested via web by Cathy Duchek
Noted on contractor print rough in ok cover
Discussed the cover of parking or housing lobby. This area wall cover was missed in noted from 9-1-17 inspection request. 345 recalls inspecting area.
Electrical Rough-In12/5/201712/6/201712/6/2017APASS
DetailsRock A. Hudson
kitchen walls, dropped ceilings live works 101-105 Phone #: ###-#### Inspection requested via web by Cathy Duchek
101 not ready, 102 thru 105 live works walls and drop lids rough in ok cover
Electrical Rough-In9/1/20179/1/20179/1/2017PPASS
DetailsJames Ady
Utility 212 wall and ceilings. corridor 211, fitness 203, management 210, business center 202, 204 and 205 restrooms dropped ceilings Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas listed ok to cover
Electrical Rough-In8/18/20178/18/20178/18/2017PPASS
DetailsRock A. Hudson
communications room 206, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Kitchen grid Rex's pizza and unit noted rough in ok cover
Electrical Rough-In8/16/20178/17/20178/17/2017APASS
DetailsRock A. Hudson
Perimeter walls in live work units 101-105 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Spray foam only on perimeter walls and ceiling OK
Electrical Rough-In7/19/20177/20/20177/20/2017PPASS
DetailsRock A. Hudson
housing lobby 106 perimeter walls, parking lobby 107 walls Phone #: ###-#### Inspection requested via web by Cathy Duchek
Noted on inspection print in office. Areas noted rough in ok cover
Electrical Rough-In5/2/20175/3/20175/3/2017PPASS
DetailsRock A. Hudson
Rough- in walls only in 2nd floor. Management office 210, corridor 211, elevator lobby 201, business center 202, corridor 208, fitness center 203, bike parking 213, restrooms 204 ; 205, dog wash 216.
Contact Fabian Luna
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted plus parcel room as noted on print in general contractors trailer wall rough in ok cover.
Electrical Rough-In2/27/20172/28/20172/28/2017AFAIL
DetailsRock A. Hudson
Lonny-fire pump Phone #: ###-####
110.26- Clear work space shall be provided for all electrical equipment in room 113 for fire pump controller. 30" wide or width of equipment and 36" deep with voltage present. Work space shall have a height of 6 1/2' minimum. Clear egress path shall also be provided. Pending additional equipment to be added.