Final | 12/11/2018 | 12/11/2018 | 12/11/2018 | P | PASS |
Eric Story
|
|
|
Frank Phone #: ###-#### Corrections fixed, Final ok
|
Final | 12/3/2018 | 12/4/2018 | 12/4/2018 | A | FAIL |
Eric Story
|
|
|
Frank Phone #: ###-#### Tamper resistant receptacles required in kitchen,master,bath Blanks required on all non used light boxes and swtiches Island outlet is required even when island is just set on floor not on wheels Lockout for dishwasher Remove temp wiring for hood
|
Electrical Rough-In | 12/14/2016 | 12/14/2016 | 12/14/2016 | P | PASS |
Eric Story
|
|
|
Frank Phone #: ###-#### Master bed and laundry plus kitchen ok cover
|
Electrical Rough-In | 12/12/2016 | 12/12/2016 | 12/12/2016 | P | NR |
Eric Story
|
|
|
Frank Phone #: ###-#### Needed conference
|
Conference | 12/12/2016 | 12/12/2016 | 12/12/2016 | P | DONE |
Eric Story
|
|
|
Frank Phone #: ###-#### Discussed nailplates and branch circuit requierments, wiring was pulled lighting circuits ran in 12 gauge and switch,branch pulled in 14 gauge will be put on a 15 amp circuit. Talked about AFCI protection and tamper resistant.
|