Permit Information
Permit NumberELE16-04045
StatusFinaled
Name APEX ELECTRIC INC
Site Address 2524 W JEFFERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Wiring a remodel.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/11/20175/12/20175/12/2017APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Greg Idsinga Final ok
Final5/11/20175/11/20175/11/2017PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Greg Idsinga
110.3- Receptacle in up bed by window shows open ground, correct or GFCI protect as per 406.4(D).
110.14- Unused openings shall be closed. 2 breaker blanks in panel.
300.4- 10-3 NM cable shall be protected from physical damage where it enters panel/meter combo.
408.41- Grounded conductors shall terminate in an individual terminal.
Electrical Rough-In12/27/201612/27/201612/27/2016PPASS
DetailsMark Moncarr
Remodel. Phone #: ###-#### Inspection requested via web by Greg Idsinga ok cover