Final | 11/7/2017 | 11/7/2017 | 11/7/2017 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by mike brown Ok final.
|
Electrical Rough-In | 5/3/2017 | 5/3/2017 | 5/3/2017 | A | PASS |
Mark Moncarr
|
|
|
trench/conduit inspection from garage to house Phone #: ###-#### Inspection requested via web by mike brown Ok cover ground work
|
Rough-In Permanent Service | 12/21/2016 | 12/21/2016 | 12/21/2016 | P | PASS |
Mark Moncarr
|
|
|
Inspection requested via web by mike brown Need to see breaker changed to 60a for garage power upon final
|
Rough-In Permanent Service | 12/20/2016 | 12/20/2016 | 12/20/2016 | A | FAIL |
Rock A. Hudson
|
|
|
ROUGH IN HOUSE AND GARAGE. PERMANENT SERVICE Phone #: ###-#### Inspection requested via web by mike brown * No access to loft above garage. 300.15- All outdoor receptacle outlets shall have boxes. Light under stair wire not in box. 300.4- SER above panel needs nail plates. 230.79- 50 amp installed and labelled for garage, shall be 60 amp minimum
|